The following basic parameters must be set for the circuit diagram shown:
Terminal
Parameter code
-
P02.01 System configuration
-
P02.22 Management of the tie breaker
(TB)
-
P08.01 Type of breaker
40 (INP1)
P12.1.01 Function of the input INP1
41 (INP2)
P12.2.01 Function of the input INP2
55 (OUT1)
P13.1.01 Function of the output OUT1
57 (OUT2)
P13.2.01 Function of the output OUT2
58 (OUT3)
P13.3.01 Function of the output OUT3
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
Settings
A: 2S-0T
OFF
Changeover pulse or changeover continuous
Source 1 breaker closed (feedback 1)
Source 2 breaker closed (feedback 2)
Close Source 1 breaker
Close Source 2 breaker
Open Source 1 and Source 2
Connection
7.2 General connection drawings
93