hit counter script

How To Determine The Default Address Of A Channel - Siemens SIMATIC S7-400 Hardware And Installation Manual

Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Addressing the S7-400
3.3

How to Determine the Default Address of a Channel

Channel on a Digital Module
A channel on a digital module is addressed bit-wise. For a digital input module with
32 inputs, four bytes (starting with the default address of the module) are used to
address the inputs, and for a digital input module with 16 inputs, two bytes are
used. Bits 0 to 7 in these bytes are then reserved by the individual inputs (from top
to bottom).
This is clarified by the following figure with the example of a digital input module
with 32 channels at slot 12 (default address 44). With a digital output module, the
first character is a Q instead of an I.
3-6
www.gkbpx.com
Channel addresses
I 44.0
I 44.1
I 44.2
I 44.3
I 44.4
I 44.5
I 44.6
I 44.7
I 45.0
I 45.1
I 45.2
I 45.3
I 45.4
I 45.5
I 45.6
I 45.7
I 46.0
I 46.1
I 46.2
I 46.3
I 46.4
I 46.5
I 46.6
I 46.7
I 47.0
I 47.1
I 47.2
I 47.3
I 47.4
I 47.5
I 47.6
I 47.7
S7-400 and M7-400 Programmable Controllers, Installation Manual
C79000-G7076-C424-01

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic m7-400

Table of Contents