6 Description of the Functions
6.4
Input/output terminals of the control board
Table 6-49
List of output signals, continued
Signal name, description
Integrator inhibit, speed controller
This output signal is used to signal whether the integral component of the speed controller is inhibited or
enabled.
1 signal
Integrator inhibit, speed controller
0 signal
The speed controller integrator is not inhibited
Parameter set
0
1st input/2
1
2nd input/2
2
3rd input/2
These 3 output signals are used to output the selected parameter set.
Parameter set
0
1st input/weighting 2
1
2nd input/weighting 2
2
3rd input/weighting 2
Note:
S
The "parameter set changeover" function is described in Chapter 6.10.
Motor 1 selected (from SW 2.4)
Motor 2 selected
Motor 3 selected
Motor 4 selected
The motor changeover contactors are controlled via these output terminal signals.
1 signal
Motor 1, 2, 3 or 4 is selected
0 signal
The motor has not been selected
Note:
S
The motor changeover version and therefore the behavior of the terminal, is selected using P1013
(motor changeover).
S
To select the motors or motor data sets, input terminal signals are available with function numbers 5
and 6 (motor data set changeover 1st input/2nd input).
S
Motor changeover is described in Chapter 6.11.
6-508
Fct. No.
0
1
2
3
0
1
0
1
0
0
1
1
0
0
0
0
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Operating
mode
n–set
pos
–
x
x
–
x
x
–
x
x
–
x
x
4
5
6
7
0
1
0
1
0
0
1
1
1
1
1
1
11
x
–
12
x
–
13
x
–
14
x
–
E Siemens AG 2005 All Rights Reserved
08.01
02.02
01.99
! 611ue diff !
PROFIBUS bit
ZSW2.6
ZSW2.0
ZSW2.1
ZSW2.2
–
–
–
–