01.99
08.01
! 611ue diff !
Table 6-49
List of output signals, continued
Signal name, description
Ready or no fault
Depending on P1012.2, this output signal indicates whether
S
The drive is ready
S
No faults present (––> "No fault" message)
if P1012.2 = "1", the following is valid:
Signal
"Ready"
1 signal
Drive is ready
0 signal
Not ready
Conditions
No faults are present
and
the board–specific pulse enable
is present (T. 663 = "1")
and
the drive–specific controller enable
is available (T. 65.x = "1")
and
the group–specific enable signals are available
(NE module, terminals 48, 63 and 64)
and
the following PROFIBUS control signals
are available:
independent of the control signals
STW1.0 = "1" (ON/OFF 1)
STW1.1 = "1" (Operating condition/OFF 2)
STW1.2 = "1" (Operating condition/OFF 3)
Note:
S
The "no fault" message is also transferred to the line supply infeed module (NE module, terminals 72,
73, 74).
S
From SW 6.1 and for P1012.12=1 a fault can also be acknowledged without STW1.0=0. However,
the drive then remains in the "Power–on inhibit" state (refer to Chapter 5.5 "Generating the power–on
inhibit"; Fig.5-9).
Parking axis selected
This output signal is used to indicate whether the axis "parks".
For a "parking axis", all of the encoder–specific monitoring and evaluation functions are disabled. This
allows the encoder to be withdrawn without initiating an alarm.
1 signal
Parking axis selected
0 signal
Parking axis not selected
Open holding brake
A motor holding brake can be controlled using an external auxiliary contactor via an output with this func-
tion.
The brake sequence control is executed in the "SIMODRIVE 611 universal".
1 signal
The auxiliary contactor for the motor holding brake is energized
0 signal
The auxiliary contactor is not energized
Note:
Refer to Chapter 6.9 for information on the motor holding brake.
E Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
6.4
(––> "Ready" message")
6 Description of the Functions
Input/output terminals of the control board
Operating
mode
Fct. No.
n–set
pos
33
x
x
if P1012.2 = "0", the following is valid:
"No fault"
There is no fault present
There is at least one fault
No faults are present
independent of terminal 663
independent of terminal 65.x
independent of the NE module
34
x
x
35
x
x
PROFIBUS bit
ZSW1.1
ZSW2.7
ZSW2.5
6-511
6