01.99
04.05
7.3.2
Error with fault/warning number
Version: 08.03.07
Reader's note
S
S
000
Alarm diagnostics not possible
Cause
– Communications to the drive have been interrupted.
– Different versions of the "SimoCom U" start-up and
Remedy
– Check the communications to the drive (cable, interfaces, ... )
– The V_611U<Version>.acc file on the hard disk of the PG/PC
harmonized
Never delete the file V000000.acc!
001
The drive does not have firmware
Cause
No drive firmware on the memory module.
Remedy
– Load the drive firmware via SimoCom U
– Insert the memory module with firmware
Acknowledgement
POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
E Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
In some instances, the space retainers (e.g. \%u) are specified for
the texts of the individual faults and warnings.
In online operation with SimoCom U instead of a space retainer, an
appropriate value is displayed.
The complete list is updated corresponding to the Edition of this
documentation (refer to the Edition in the header lines) and
corresponds to the software release of "SIMODRIVE 611 universal"
documented here.
The individual faults/warnings are not coded dependent on the
software release.
parameterizing tool and the drive.
should be adapted to the drive as follows:
– Exit "SimoCom U"
– Delete the V_611U<Version>.acc file (search and delete the file)
– Restart "SimoCom U" and go online
The V_611U<Version>.acc file is now re-generated and is
to the drive version.
7 Fault Handling/Diagnostics
7.3
List of faults and warnings
7
7-629