NTP-G7 Install the Power and Ground

NTP-G7 Install the Power and Ground
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Warning
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Statement 1003
Warning
This equipment is intended to be grounded. Ensure that the host is connected to earth ground during
normal use. Statement 39
Cisco ONS 15454 Hardware Installation Guide
68
This procedure installs power feeds and grounds the ONS 15454.
ANSI and ETSI:
• #2 Phillips Dynamometric screwdriver
• Medium slot-head screwdriver
• Small slot-head screwdriver
• Screws
• Ground cable 13.3-mm² (#6 AWG) stranded
• Listed pressure terminal connectors such as ring and fork types; connectors
must be suitable for #10 AWG copper conductors
• Wire cutters
• Wire strippers
• Crimp tool
• Fuse panel
ANSI only:
• Power cable (from fuse and alarm panel to assembly), #10 AWG, copper
conductors, 194 degrees F [90 degrees C])
• Wire wrapper
ETSI only:
• Power cable (from fuse panel to MIC-A/P and to MIC-C/T/P), shipped with
the ONS 15454 ETSI
• Two-hole grounding lug, shipped with the ONS 15454 ETSI
NTP-G4 Open and Remove the FMEC Cover (ETSI Only), on page 60
NTP-G6 Install the MIC-A/P and MIC-T/C/P FMECs (ETSI Only), on page 66
NTP-G5 Remove the Backplane Covers (ANSI Only), on page 63
Required
Onsite
None
Installing the ONS 15454 M12 (ANSI and ETSI) Shelf