12 ERROR CODE LISTS
Error
Details
code
code
Name
Indirect specified 64-
16467
—
bit data register
(D(n)F) read error
Indirect specified 16-
16468
—
bit link register (W(n))
read error
Indirect specified 32-
16469
—
bit link register
(W(n)L) read error
Indirect specified 64-
16470
—
bit link register
(W(n):F) read error
Indirect specified
16475
—
SM(SM(n)) read error
Direct specified
Multiple CPU area
device bit specified for
16482
—
CPU No.1
(U3E0\G10000.0 to)
read error
Direct specified
Multiple CPU area
device bit specified for
16483
—
CPU No.2
(U3E1\G10000.0 to)
read error
Direct specified
Multiple CPU area
device bit specified for
16484
—
CPU No.3
(U3E2\G10000.0 to)
read error
Direct specified
Multiple CPU area
device bit specified for
16485
—
CPU No.4
(U3E3\G10000.0 to)
read error
Indirect specified input
16486
—
relay (X(n)) read error
Indirect specified
16487
—
output relay (Y(n))
read error
Indirect specified
16488
—
internal relay (M(n))
read error
Indirect specified link
16489
—
relay (B(n)) read error
Annunciator (F(n))
16490
—
read error
Indirect specified 16-
16516
—
bit batch input relay
(X(n)) read error
Indirect specified 32-
16517
—
bit batch input relay
(X(n)) read error
Indirect specified 16-
16518
—
bit batch output relay
(Y(n)) read error
Indirect specified 32-
16519
—
bit batch output relay
(Y(n)) read error
Error factor
Description
The indirectly specified device No. is outside
the range or an odd number.
The indirectly specified device No. is outside
the range.
The indirectly specified device No. is outside
the range or an odd number.
The indirectly specified device No. is outside
the range.
Multiple CPU area device number is outside
the range set in the parameter.
Multiple CPU area device number is outside
the range set in the parameter.
The indirectly specified device No. is outside
the range.
The indirectly specified device No. is
outside the range or is not a multiple of 16.
12 - 20
Error Processing
Correct the program so that the indirectly
specified device No. is proper.
Correct the program so that Multiple CPU
area device number is within the range set in
the parameter.
The block processing
in execution is
stopped and the next
block is executed.
Correct the program so that the indirectly
specified device No. is proper.