Technical Data
5.1 Device Data
5.1
Device Data
Supply Voltage
Auxiliary voltage – direct voltage
Permissible ripple of the DC input voltage
Power consumption
Maximum inrush current at ≤ 110 V
Maximum inrush current at 220 V to 300 V
Efficiency level
Auxiliary voltage – alternating voltage
Permissible higher harmonics
Maximum inrush current at ≤ 115 V
Maximum inrush current at 230 V
Power consumption
Power-failure backup
Output-voltage status display
Fault-Signaling Connection (Relay)
Relay
Maximum contact voltage with a resistive load
Maximum switching current
Maximum switching power
Permissible current for contacts
Test voltage
Fuses
Not replaceable
Replaceable
Safety
As per DIN EN 61010 Part 1, overvoltage category
Degree of pollution
Fire-resistance rating as per UL 94
42
DC 24 V to 250 V (± 20 %)
15 %
8 W
< 15 A
≤ 22 A
After 250 μs: < 5 A
> 50 % at rated load
AC 60 V to 230 V (± 20 %) at 45 Hz to 65 Hz
2 kHz
< 15 A
≤ 22 A
After 250 μs: < 5 A
18 VA
Min. 50 ms at rated load
1 green LED to display the operating state
MSR relay, 1 break contact, isolated; 2-pole terminal
AC 240 V
5 A
AC 2000 VA
5 A
V
= 3.51 kV
RMS
T 2.0 A
T 1.6 A at AC 250 V or DC 300 V
III
2
V0
Accessories, Mini Star Coupler, Manual
C53000-G9050-C595-1, Edition 05.2020