RMA805 Enraf FlexLine Remote Indicator
User's Manual
34-ST-25-67
Revision 1.0
August 2020
Honeywell Process Solutions

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Enraf FlexLine RMA805

  • Page 1 RMA805 Enraf FlexLine Remote Indicator User's Manual 34-ST-25-67 Revision 1.0 August 2020 Honeywell Process Solutions...
  • Page 2: Copyrights, Notices And Trademarks

    In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
  • Page 3 About this Document This guide provides the details of Honeywell RMA805 Enraf FlexLine Remote Indicator for applications with Honeywell Enraf FlexLine Gauges. Release Information Document Name Document ID Release Publication Date Number RMA805 Enraf FlexLine Remote Indicator #34-ST-25-67 User’s Manual...
  • Page 4 Symbol Definitions The following table lists those symbols used in this document to denote certain conditions. Symbol Definition ATTENTION: Identifies information that requires special consideration. TIP: Identifies advice or hints for the user, often in terms of performing a task. REFERENCE -EXTERNAL: Identifies an additional source of information outside of the bookset.
  • Page 5 Symbol Definition Earth Ground: Functional earth connection. NOTE: This connection shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements. Chassis Ground: Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements.
  • Page 6 EEPROM Electrically Erasable Programmable Read Only Memory Electromagnetic Interference FCI-HRT An interface module inside a FlexLine Gauge FlexLine Type of Gauge used in Honeywell Tank Storage devices Gauge Measurement device. HART Highway Addressable Remote Transmitter Process Variable Printed Wiring Assembly...
  • Page 7: Table Of Contents

    Contents COPYRIGHTS, NOTICES AND TRADEMARKS ........II INTRODUCTION ................1 About the RMA805 Enraf FlexLine Remote Indicator ........1 Features and Options ..................1 Remote Indicator Components ..............2 Specifications ....................3 Dimensions ...................... 4 Remote Indicator Nameplate ................5 Safety Certification Information ..............
  • Page 8 MAINTENANCE ................22 Overview ......................22 Preventive Maintenance ................22 Upgrading the Firmware ................22 TROUBLESHOOTING ..............23 Overview ......................23 Critical Diagnostic Screens ................23 5.2.1 Fault Conditions and Recommended Corrective Actions ........24 SECURITY ................... 25 Security Guidelines ..................25 viii RMA805 Enraf FlexLine Remote Indicator User’s manual Revision 1...
  • Page 9 Tables Table 1: Features and Options ................1 Table 2: Specifications ..................3 Table 3: Main Menu Structure ................. 13 Table 4: Display Setup Menu ................13 Table 5: Device Setup Menu ................14 Table 6: Information Menu ................14 Table 7: Diagnostic Menu ................
  • Page 10 Figures Figure 1: Remote Indicator Housing ..............2 Figure 2: Electronic Housing Components ............2 Figure 3: Dimensions of the Remote Indicator ..........4 Figure 4: Detail of typical Remote Indicator Nameplate ........5 Figure 5: Pipe Mount - Horizontal Mounting Bracket ......... 7 Figure 6: Pipe Mount - Vertical Mounting Bracket ..........
  • Page 11: Introduction

    The RMA805 Enraf FlexLine Remote Indicator provides a means of remote-mounting a display that is associated with a Honeywell Enraf FlexLine Gauge. The Remote Indicator can be located hundreds of meters away from the FlexLine Gauge providing easy access to data.
  • Page 12: Remote Indicator Components

    Remote Indicator Components The following illustrations depict the housing and electronic components. Figure 1: Remote Indicator Housing Figure 2: Electronic Housing Components RMA805 Enraf FlexLine Remote Indicator User’s manual Revision 1...
  • Page 13: Specifications

    Operative 5 – 100% RH Transportation/Storage 5 – 100% RH Design Specifications To be used with Honeywell Enraf FlexLine Gauges only. Electrical Compatibility See note 1. To be used with Honeywell Enraf FlexLine Gauges only. Functional Compatibility See note 1.
  • Page 14: Dimensions

    Dimensions millimeters Reference Dimensions: inches Figure 3: Dimensions of the Remote Indicator Note 1: Housing adapter may not be present on all transmitter models. If the housing adapter is not present, subtract 24,5mm (0,96 inches) from the dimension specified. RMA805 Enraf FlexLine Remote Indicator User’s manual Revision 1...
  • Page 15: Remote Indicator Nameplate

    Remote Indicator Nameplate The Remote Indicator name plate at the top of the electronics housing (see Figure 1) lists model number, physical configuration, electronics options, accessories, certifications, and manufacturing specialties. Figure 4: Detail of typical Remote Indicator Nameplate Identification of the series and basic Remote Indicator type is captured in the last digit in the key number.
  • Page 16: Installation And Startup

    Mounting the Remote Indicator Remote Indicator models can be attached to a two-inch (50.8 millimeter) vertical or horizontal pipe using Honeywell’s optional pipe mounting bracket. The Remote Indicator can also be wall mounted using Honeywell’s optional wall mounting bracket as shown in Figure 2.3.1...
  • Page 17: Figure 5: Pipe Mount - Horizontal Mounting Bracket

    Figure 5: Pipe Mount - Horizontal Mounting Bracket Figure 6: Pipe Mount - Vertical Mounting Bracket Revision 1 RMA805 Enraf FlexLine Remote Indicator User’s manual...
  • Page 18: Figure 7: Mounting Bracket Secured To A Remote Indicator

    Figure 7: Mounting Bracket Secured to a Remote Indicator 3. Position the bracket on a 2-inch (50.8 mm) horizontal or vertical pipe, and install a “U” bolt around the pipe and through the holes in the bracket. Secure the bracket with (2) M10 hex nuts, (2) flat washers and (2) lock washers provided.
  • Page 19: Wall Mounting Procedure

    2.3.3 Wall Mounting Procedure Wall Mount Option – Refer to Figure 9 Position the bracket on the mounting surface at the desired location and secure the bracket to the mounting surface using the appropriate hardware (Wall mounting hardware requirements to be determined and supplied by the end user). Figure 9: Remote Indicator Secured to a Wall Mounting Bracket Revision 1 RMA805 Enraf FlexLine Remote Indicator User’s manual...
  • Page 20: Wiring A Remote Indicator

    Wiring a Remote Indicator 2.4.1 Introduction The Remote Indicator must be connected to the local HART compatible bus of the Enraf Smartradar FlexLine or the Enraf SmartServo 954. 2.4.2 Terminal Block The Remote Indicator has 3 terminals. Following table provides the connection details: Terminal Description Loop +...
  • Page 21: Electrical Wiring

    2.4.3 Electrical Wiring The Remote Indicator shall be connected to the Loop + and Loop - terminals of the FlexLine Gauge. Typically, these are terminals 24 and 25. See the installation manual of the FlexLine Gauge for more information. It is possible that other devices such as a VITO temperature convertor and a pressure transmitter must be connected to the same loop.
  • Page 22: Operation

    Operation Overview This section provides information the RMA805 Enraf FlexLine Remote Indicator operation and configuration. All interaction with the Remote Indicator is done via the Advanced Display and the 3-button interface on the top of the device. There are two types of interaction. The user can press the  button to activate the Online screen or ↵...
  • Page 23: Selecting A New Setting From A List Of Choices

    3.2.2 Selecting a New Setting From a List of Choices Use the procedure described below to select a new setting for parameters that present a list of choices (e.g., PV display, Temperature Units, Pressure Units etc.). ↵ 1. Press to begin the edit process. o The Standard Display will show the current setting of the item on the lower line.
  • Page 24: Device Setup Menu

    3.3.2 Device Setup Menu FlexLine Gauges are capable of driving 2 displays at the same time. However only 1 display can be showing actual data. Each device must have a different HART address. Only HART address 7 or 8 is allowed. Each display can be activated by pressing a button.
  • Page 25: Errors And Diagnostics

    Errors and Diagnostics 3.4.1 Diagnostics Menu Table 7: Diagnostic Menu <Return> Return to the Level 1 menu <Return> Critical FAULT: There is a problem with the Comm Module FAULT Communications Module. <Return> LOW: Supply voltage is below the low specification limit Supply Voltage Non-Critical HIGH: Supply voltage is above the...
  • Page 26: Operational

    Firmware versions After the initial startup screen the Remote Indicator will briefly show the currently installed firmware versions for both the Display and the Communication modules. Offline state In the event this scrren is displayed, the Remote Indicator is powered on but there is no digital communication with the FCI-HRT established yet.
  • Page 27 Online Online display with data received from FlexLine Gauge. Revision 1 RMA805 Enraf FlexLine Remote Indicator User’s manual...
  • Page 28: The Online Display

    3.5.3 The Online Display The online display is divided in three main parts The top half of the Display shows the product level data as sent by the FlexLine Gauge to the Remote Indicator. Formatting, number of digits, decimal separator, Units, Various status information characters and the level type are all defined in the FlexLine Gauge.
  • Page 29: Errors And Diagnostics

    Errors and Diagnostics Table 10: Errors and Diagnostics Display Indicator What it means Flashing D in bottom left corner. Non-Critical Diagnostic condition present Look in the diagnostics menu for more information. Critical Diag A black band in middle of the display with white on black text; Critical Diag indicates that a Critical Diagnostic condition is present.
  • Page 30: Setting The Jumpers

    Setting the Jumpers On the Remote Indicator there is a failsafe jumper and a write protect jumper behind the display on the Communication Module. The top jumper is the failsafe jumper. The bottom jumper sets the write protect. Since the Remote Indicator is intended to be used in Digital Multidrop mode only it is highly recommended to put the failsafe jumper to DOWN (Downscale).
  • Page 31: Table 11: Jumper Settings

    Table 11: Jumper Settings Image Description Failsafe = DOWN (3.8mA) Write Protect = OFF (Not Protected) Failsafe = UP (21.8mA) NOT RECOMMEND Write Protect = OFF (Not Protected) Failsafe = DOWN (3.8mA) Write Protect = ON (Protected) Failsafe = UP (21.8mA) NOT RECOMMEND Write Protect = ON (Protected) 1.
  • Page 32: Maintenance

    Maintenance Overview This section provides information about preventive maintenance and upgrading firmware. Preventive Maintenance The RMA805 Enraf FlexLine Remote Indicator does not require any specific maintenance at regularly scheduled intervals. Maintenance of the Remote Indicator is limited to ensuring that connections, seals and mounting are tight and secure.
  • Page 33: Troubleshooting

    Remote Indicator devices and the recommended actions to correct them. Troubleshooting is performed to determine the cause of the fault by analyzing the device indications or diagnostics messages. If you require assistance, contact your distributor or Honeywell Technical Support. Critical Diagnostic Screens When a critical diagnostic is present figure 15 shows how this is indicated on the display.
  • Page 34: Fault Conditions And Recommended Corrective Actions

    5.2.1 Fault Conditions and Recommended Corrective Actions Table 12: Fault Conditions and Recommended Corrective Actions. Condition Analysis Recommended/Corrective Action Blank display The Remote Indicator has no power Check that the gauge the Remote Indicator is connected to is powered on and working correctly.
  • Page 35: Security

    Honeywell investigates all reports of security vulnerabilities affecting Honeywell products and services. To report potential security vulnerability against any Honeywell product, please follow the instructions at: https://honeywell.com/pages/vulnerabilityreporting.aspx Submit the requested information to Honeywell using one of the following methods: •...
  • Page 36 For application assistance, current specifications, ordering, pricing, and name of the nearest Authorized Distributor, contact one of the offices below. ASIA PACIFIC EMEA Americas Honeywell Pte Ltd. Honeywell Enraf Honeywell Enraf Americas, Inc. 17 Changi Business Park Delftechpark 39 1250 West Sam Houston Pkwy S. Central 1 2628 XJ Delft Houston, TX 77042,...