2.8 Electronic trip unit ETU
Protection functions of the ETU
Switchover to the alternative of the external,
directly measured ground-fault protection
Switchover to alternative operating values with
ground-fault current during the switch-on phase
(inrush adaptation) for tripping characteristic t=k
(fixed) possible
Setting range of the switch-on phase (inrush
adaptation)
Setting range I
phase (inrush adaptation)
Extended parameter range with ext. auxiliary
power supply of the ETU
G direct
GF direct: Ground-fault protection direct measu-
rement
Protection function can be selected
R
- residual-current protection
•
c
(with summation current transformer)
G
- ground-fault return protection
•
ret
(transformer in the star point)
Rc - residual-current protection
(with summation current transformer)
Setting range operating value residual current
I
∆n
Setting range for delay time t
Gret ground-fault return protection
(ground return - transformer in the star point)
Design of G
ret
(ground fault return CT, I
Setting range operating value ground fault re-
turn I
= I
g_ret
CT_rating
Setting range of delay time t
Setting range for delay time t
rence point 4 x I
76
= I
x ... during the switch-on
g
n
∆n
transformer
)
CT_rating
x ...
(fixed) t=k
g_ret
at I²t (refe-
g_ret
)
n
ETU650 LSI
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
ETU660 LSIG
●
Default value: OFF
●
Default value: OFF
0.1 to 30 s (in steps of 0.01)
Default value: 0.1
0.2 to 1 (in steps of 0.01)
Default value: 1
- I
full range,
g
otherwise I
limited to
g
min. 0.2 I
or 0.25 I
(for
n
n
I
= 400A)
n
- t
possible instantaneously
g
●
Default set: Not installed
Ground return CT; Rc CT;
necessary
●
Alternative to GF and G_ret
Default value: OFF
Possible with current sensor
Rc & MF advanced
3; 5; 7; 10; 20; 30 A
Default value: OFF
Possible with current sensor
Rc & MF advanced
0.06; 0.1; 0.2; 0.3; 0.4; 0.5;
0.8 s
●
Alternative to GF and Rc
100; 250 A
Default value: 100 A
0.1 to 1 x I
(in steps of
CT_rating
0.001)
Default value: 0.1
0.1 to 1 s (in steps of 0.05)
Default value: 0.1s
0.1s to 1s (in steps of 0.05)
Manual, 10/2018, L1V30499596002-01