1 Alarms
20108
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
20109
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
20120
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
20121
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
1-292
Invalid data package received from the digitizer. Error codes: %1, %2
%1 = Error code of cyclic packet
%2 = Error code of out-of-band packet
A data packet received by the digitizing unit could not be evaluated.
- Alarm display.
- Interface signals are set.
- Channel not ready.
- NC Stop on alarm.
- NC Start disable in this channel.
Please inform the authorized personnel/service department. Error code: 0, 0: Check cable
connection leading to the NC. Other error codes: e.g. wrong header, incorrect checksum
(development documentation).
Clear alarm with the RESET key. Restart part program
Error in communication with the digitizer: status code of com-circuit: %1
%1 = Status byte
The circuit for serial communication with the digitizing unit signals a transmission error via
its status byte (framing error, parity etc.).
- Alarm display.
- Interface signals are set.
- Channel not ready.
- NC Stop on alarm.
- NC Start disable in this channel.
Please inform the authorized personnel/service department. Check connection cable
leading to the digitizing unit: In particular screening.
Clear alarm with the RESET key. Restart part program
Axis %1: too many compensation relations
%1 = Axis name, spindle number
IInterpolatory compensation with tables. For each axis, the maximum number of compen-
sation relationships defined may be no more than the number of axes in the system. In
this alarm, the interpolatory compensation in the axis is switched off automatically.
- Alarm display.
- Interface signals are set.
Check table parameters $AN_CEC_OUTPUT_AXIS and correct and/or switch off one or
more tables ($SN_CEC_TABLE_ENABLE).
Clear alarm with the RESET key. Restart part program
Axis %1: Configuration error in compensation table %2
%1 = Axis name, spindle number
%2 = Compensation table
IInterpolatory compensation with tables. The settings for the specified table are not
allowed. $AN_CEC_MAX >= $AN_CEC_MIN and $AN_CEC_STEP != 0 apply to system
variables. This table is switched off automatically.
- Alarm display.
- Interface signals are set.
Please inform the authorized personnel/service department. Check and correct the char-
acteristic data in the compensation table. If the error cannot be found, the alarm can be
suppressed by switching off the table ($SN_CEC_TABLE_ENABLE) or switching off com-
pensation in the axis ($MA_CEC_ENABLE).
Clear alarm with the RESET key. Restart part program