Assignment of NCK input/output byte via MD %1[%2] does not match hardware
configuration
%1 = String: MD identifier
%2 = MD array index
When booting, the required input/output module was not found at the slot specified in the
MD.
- Alarm display.
- Interface signals are set.
- NC not ready.
- Channel not ready.
- NC Start disable in this channel.
- NC Stop on alarm.
Please inform the authorized personnel/service department. Check hardware and correct
the MD if necessary. Note: Monitoring of the hardware configuration is performed inde-
pendently of the number of activated inputs/outputs (MD 10300 - 10360
FASTIO_ANA(DIG)_NUM_INPUTS(OUTPUTS))
Switch control OFF - ON.
Hardware of external NCK outputs assigned repeatedly
Several outputs have been configured on the same hardware byte.
- Alarm display.
- Interface signals are set.
- NC not ready.
- Channel not ready.
- NC Start disable in this channel.
- NC Stop on alarm.
Please inform the authorized personnel/service department. Alter MD 10364
HW_ASSIGN_DIG_FASTOUT or MD 10364 HW_ASSIGN_ANA_FASTOUT.
Switch control OFF - ON.
Error on terminal block %1, error code %2
%1 = Number of terminal block (1 ... 4)
%2 = Error code
An error occurred on terminal block no. %1 (sign-of-life failure, I/O module removed in
current operation, etc.). All possible errors which can lead to this alarm are not yet known
(and will be completed later). Further information together with a description of the error
code and its meaning will be provided at a later date.
Error code 1: Sign-of-life failure from terminal block
Error code 10: Sign-of-life failure NC
- Alarm display.
- Interface signals are set.
- NC not ready.
- Channel not ready.
- NC Start disable in this channel.
- NC Stop on alarm.
Please inform the authorized personnel/service department. Check hardware.
Switch control OFF - ON.
Local P-bus sign-of-life monitoring
The COM computer must alter the sign-of-life on the local P-bus in each SERVO cycle.
Monitoring for alteration takes place in the IPO cycle. If the sign of life has not altered, this
alarm is triggered.