1 Alarms
Reactions:
Remedy:
Program Continuation:
14530
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
14540
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
14541
Parameters:
Definitions:
Reactions:
1-212
- Correction block is reorganized.
- Interface signals are set.
- Alarm display.
Modify NC part program appropriately.
Clear alarm with NC START or RESET key and continue the program.
Channel %1 block %2 EXTERN and PROC instruction do not correspond
%1 = Channel number
%2 = Block number, label
Subroutines with parameter transfer must be known before they are called in the program.
If the subroutines are always available (fixed cycles) the control establishes the call inter-
faces at the time of system power-up. Otherwise an EXTERN statement must be pro-
grammed in the calling program.
Example:
N123 EXTERN UPNAME (TYP1, TYP2, TYP3, ...)
The type of the variable must match the type given in the definition (PROC statements) or
it must be compatible with it. The name can be different.
- Interpreter stop
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
Check the variable types in the EXTERN and the PROC statements for correspondence
and correctness.
Clear alarm with the RESET key. Restart part program.
Channel %1 block %2 contour tool: the min. limit angle has been programmed more
than once (edge D%3)
%1 = Channel number
%2 = Block number, label
%3 = Edge number, label
The limit angle of a contour tool must be equal zero in an involved edge only.
- Correction block is reorganized.
- Local alarm reaction.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm at block end.
Change tool definition
Clear alarm with NC START or RESET key and continue the program.
Channel %1 block %2 contour tool: the max. limit angle has been programmed
more than once (edge D%3)
%1 = Channel number
%2 = Block number, label
%3 = Edge number, label
The limit angle of a contour tool must be equal zero in an involved edge only.
- Correction block is reorganized.
- Local alarm reaction.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm at block end.