hit counter script

Siemens SINUMERIK 840D Diagnostics Manual page 613

Hide thumbs Also See for SINUMERIK 840D:
Table of Contents

Advertisement

10.04
Definitions:
Reactions:
Remedy:
Program Continuation:
300915
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
300950
Parameters:
Definitions:
 Siemens AG, 2004. All rights reserved
SINUMERIK 840D/840Di/810D Diagnostics Guide (DA), 10.04 Edition
The drive is disabled by the reaction configured in MD 1361:
$MD_SAFE_VELO_STOP_MODE. At the end of the stop reaction, the drive remains
under control, the axis is monitored for SBH.
Request: In monitoring cycle.
The axis has moved faster than allowed in machine data MD 1331:
$MD_SAFE_VELO_LIMIT[n] (safe velocity limit values). If the "safe velocity correction"
function is enabled in MD1301: $MD_SAFE_FUNCTION_ENABLE (safe functions
enable), allowance must be made for the correction factor in the velocity limit when using
SG2 and SG4.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Please inform the authorized personnel/service department. Check the input values of the
machine data. Check the safe input signals: is the correct one of four velocity limits
selected?
Clear alarm with the RESET key. Restart part program
Axis %1 drive %2 safe end positions exceeded
%1 = Axis number
%2 = Drive number
The drive is disabled by the reaction configured in MD 1362:
$MD_SAFE_POS_STOP_MODE. At the end of the stop reaction, the drive remains under
control, the axis is monitored for SBH.
Request: In monitoring cycle.
The axis has exceeded the limit position which is entered in
• Modify MD 1334: $MD_SAFE_POS_LIMIT_PLUS[n] (upper limit for safe end position)
• Modify MD 1335: $MD_SAFE_POS_LIMIT_MINUS[n] (lower limit for safe end position)
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Please inform the authorized personnel/service department. If no obvious operator error
occurred: Check the input value of the machine data and check the SGEs: was the correct
one of 2 end positions selected? If the MDs and SGEs are o.k., check the machine for any
damage and rectify.
Clear alarm with the RESET key. Restart part program
Axis %1 drive %2 is not safely referenced
%1 = Axis number
%2 = Drive number
No stop reaction is initiated. The message will be present during enabling of the functions
SN/SE until the axis status "Axis safely referenced" has been reached.
Request: In monitoring cycle.
1) The axis is not referenced or
2) The user enable for this axis is missing or was canceled. This can occur, for example, if
the axis was moved after the machine was switched off and the standstill position which
was stored is therefore no longer correct.
This message prompts the user to confirm the actual position. To do this, you must deter-
mine the position, e.g. as follows:
• Measure the position.
• Move to a known position.
1 Alarms
1-613

Advertisement

Table of Contents
loading

Table of Contents

Save PDF