1 Alarms
Reactions:
Remedy:
Program Continuation:
8044
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
8045
Definitions:
Reactions:
Remedy:
Program Continuation:
8080
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
8081
Parameters:
1-86
- Mode group not ready.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
- Channel not ready.
--
Switch control OFF - ON.
Option for IPO cycle time %1 ms not set
%1 = Impermissible IPO cycle time
The option for activation of an IPO cycle time of %1 ms has not been set.
Option - Permiss. IPO cycle time:
• Option-free >= 8ms
• 1. step >= 6ms
• 2. step >= 4ms
• 3. step >= 2ms
• 4. step <2ms
- Interpreter stop
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
• Buy option
• Increase IPO cycle time (e.g. via MD IPO_SYSCLOCK_TIME_RATIO)
Switch control OFF - ON.
Option for selected cycle settings not set
The option for the 810D Powerline for activation of the same current/speed/position con-
troller/IPO cycle time grid as with the 840D is not set. Without the option, only the set val-
ues of the 810D Standard are permitted.
- Interpreter stop
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
• Buy option
• Set (current/speed controller) cycle times to 810D default values.
Switch control OFF - ON.
%1 options are activated without setting the license key
%1 = Number of non-licensed options
An option was activated but no license key set to prove the purchase of the option.
- Alarm display.
Generate and enter license key via Internet.
Clear alarm with the Delete key or NC START.
%1 options are activated that are not licensed by the license key
%1 = Number of non-licensed options