Page 1
Preface Data in the PROFIBUS-DP messages SIPROTEC4 Standard mapping 2-1 Multifunction protection with Standard mapping 2-2 control Standard mapping 2-3 7SJ61...63, 7SJ65 Standard mapping 2-4 Input/Output unit with local control Glossary 6MD63 Index Communication module Cover PROFIBUS-DP Bus mapping Revision: 2.1 Edition: October 2001 C53000-L1840-B006-02...
Page 2
Registered trademarks Subject to change without prior notice. SIPROTECâ und DIGSIâ are registered trademarks of Siemens AG. Other designations in this manual may be trademarks that if used by third parties for their own purposes may violate the rights of the owner.
Page 3
Preface The manual is devided into the following topics: Contents of this manual • Data in the PROFIBUS-DP messages • Standard mapping 2-1 • Standard mapping 2-2 • Standard mapping 2-3 • Standard mapping 2-4 This manual describes the data in the PROFIBUS-DP messages of the Additional SIPROTEC devices 7SJ61...7SJ63, 7SJ65, 6MD63.
Page 4
See our catalog of courses for a list of available courses or contact our Training courses Training center in Nuremberg. Questions If you have questions to the SIPROTEC devices, contact your Siemens representative. 7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping C53000-L1840-B006-02...
Page 5
Revision index Modified chapters / Edition Reasons of modification pages First edition, Doc.-No.: C53000-L1840-B006-02 Aug 23 , 2000 • Document also valid for 7SJ65 devices • chap. 4.2.3.1 Allocation 3/0...3/7 for Standard mapping 2-3 corrected • chap. 5 Standard mapping 2-4 added chap.
Page 6
Revision index 7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping C53000-L1840-B006-02...
Table of contents Data in the PROFIBUS-DP messages................1-1 Explanation..................... 1-1 Messages in output direction: PROFIBUS-DP master to the SIPROTEC device ......................1-3 Messages in input direction: SIPROTEC device to the PROFIBUS-DP master ......................1-3 1.3.1 Annunciations....................1-3 1.3.2 Measured values .................... 1-4 1.3.3 Metered measurands ..................
Page 8
Table of contents 2.2.1.5 Diagnosis........................2-5 2.2.1.6 Automatic recloser status ....................2-6 2.2.1.7 Time overcurrent protection..................2-6 2.2.1.8 Directional time overcurrent protection................2-7 2.2.1.9 Unbalanced load protection..................2-7 2.2.1.10 Frequency protection ....................2-7 2.2.1.11 Undervoltage and overvoltage protection ..............2-8 2.2.1.12 Sensitive ground fault protection.................2-8 2.2.1.13 Circuit breaker failure protection .................2-8 2.2.1.14 Thermal overload protection ..................2-9 2.2.1.15...
Page 9
3.2.1.15 Cold load pickup ......................3-8 3.2.1.16 Measurement supervision...................3-8 3.2.1.17 Set point alarms ......................3-8 3.2.1.18 Status annunciations ....................3-9 3.2.2 Measured values ..................3-10 3.2.2.1 Recorded measured values ..................3-10 3.2.2.2 Measured values – mean values................3-10 3.2.3 Metered measurands ................... 3-10 Standard mapping 2-3 ....................4-1 Message in output direction ................
Page 10
Table of contents 5.2.1.5 Sensitive ground fault protection ................5-14 5.2.1.6 Thermal overload protection..................5-14 5.2.1.7 Directional time overcurrent protection..............5-14 5.2.1.8 Diagnosis........................5-14 5.2.2 Measured values ..................5-15 5.2.3 Metered measurands ................... 5-15 Glossary .......................... 6-1 Index ..........................7-1 7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping viii C53000-L1840-B006-02...
Data in the PROFIBUS-DP messages Data in the PROFIBUS-DP messages Explanation Note The examples shown in this chapter 1.1 do not necessarily correspond to the real allocation of the objects in the bus mapping. The chapters 2 to 5 define the data area of the PROFIBUS-DP messages for data transfer between the PROFIBUS-DP slave of the SIPROTEC device 7SJ61...7SJ63, 7SJ65, 6MD63 with the PROFIBUS- DP master.
Page 12
Data in the PROFIBUS-DP messages Bit variables The offset indicates the byte, which contains the bit value and the position of bit 0 of the bit variable, e.g. (input message): (SP/SC, DP/DC) Offset Designation of the Comments Internal SIPROTEC objects object no.
Data in the PROFIBUS-DP messages Messages in output direction: PROFIBUS-DP master to the SIPROTEC device The messages in PROFIBUS-DP output direction (ref. to chap. 2.1, 3.1, 4.1 and 5.1) allow: • command outputs through the output relays of the SIPROTEC device (external commands), •...
Data in the PROFIBUS-DP messages 1.3.2 Measured values Note Depending on the device composition not all of the indicated analog inputs (and corresponding PROFIBUS-DP message positions) may be available in the SIPROTEC device. The given scaling values for the measured values in the standard mappings apply to installations with the following nominal operating values: Nominal operating voltage of primary equipment (parameter address 1101):...
Data in the PROFIBUS-DP messages 1.3.3 Metered measurands Scaling The scaling of the metered measurands, which are derived from measured values, refers to: 60000 impulses per hour for V = V and I = I OMINAL OPERATING VOLTAGE OF PRIMARY EQUIPMENT (parameter address = 1101) OMINAL OPERATING CURRENT OF PRIMARY EQUIPMENT (parameter address = 1102)
Data in the PROFIBUS-DP messages Configuration data of the standard mappings 2-1 to 2-4 There are three standard mappings (standard mapping 2-1 to standard mapping 2-4) available for the SIPROTEC devices 7SJ61...7SJ63, 7SJ65, 6MD63 for parameterization with DIGSI version 4.2 or higher which differ in the data size of the PROFIBUS-DP messages.
Page 17
Data in the PROFIBUS-DP messages Standard The standard mapping 2-4 contains: mapping 2-4 Output direction: • 3 double-point commands • 5 single-point commands Input direction: • 3 double-point indications • 26 single-point indications • 8 measured values (integer) • 2 metered measurands (unsigned long) PROFIBUS-DP Standard mapping 2-1: 1FH 1FH 1FH 1FH 1FH 1FH 13H 28H configuration data...
Page 18
Data in the PROFIBUS-DP messages Standard mapping 2-3: Module Order number Input Output address address Input – 16 Bytes Addr_Ix Input – 16 Bytes Addr_Ix+16 Input – 16 Bytes Addr_Ix+32 Input – 16 Bytes Addr_Ix+48 Input – 16 Bytes Addr_Ix+64 Output –...
Page 19
Data in the PROFIBUS-DP messages The DIGSI 4.1 standard mappings are not component of this documentation. You find associated information in the following manuals: Manual Contents Order number PROFIBUS-DP C53000-L1840-B002-01 Data in the PROFIBUS-DP messages Bus mapping of the SIPROTEC device 7SJ61 7SJ61 PROFIBUS-DP C53000-L1840-B003-01...
Data in the PROFIBUS-DP messages Notes to SIPROTEC objects This chapter contains notes for the use and evaluation of certain SIPROTEC objects. The description of the standard mappings (ref. to chap. 2 to 5) contains the pre-allocation of the mapping files at delivery or first assignment of a mapping in DIGSI to the SIPROTEC device.
Data in the PROFIBUS-DP messages 1.5.2 Control mode REMOTE Control mode with control authority is REMOTE, option of unlocked control with PROFIBUS-DP. • Changing the “Control mode REMOTE“ to UNLOCKED permits one unlocked control operation via PROFIBUS-DP. After execution of the command, the “Control mode REMOTE“...
Data in the PROFIBUS-DP messages 1.5.4 CFC-Incoming annunciations The CFC-Incoming annunciations allow routing of further protection annunciations on PROFIBUS-DP, which are not contained in the standard mapping (e.g. ">BLK 50/51", internal object number = 1704 or ">BLK 50N/51N", internal object number = 1714). You find information about this in the manual "7SJ61...63, 7SJ65, 6MD63, 7UM61 PROFIBUS-DP - Communication profile"...
Data in the PROFIBUS-DP messages 1.5.6 Alarm summary event The "Alarm summary event" is indicated, if at least one of the following internal alarms assumes the ON status: • "Failure: Current summation“, "Failure: Current balance“, "Failure: Voltage balance“, "Failure: Phase sequence current“, "Failure: Phase sequence voltage“.
Data in the PROFIBUS-DP messages Using device firmware version 4.3 or higher The following SIPROTEC objects are no longer included per default in the parameter set of the device. Double commands: • Switching device D1 (UsrDC1) ... Switching device D3 (UsrDC3) Single commands: •...
Standard mapping 2-1 Offset Designation of the Internal Comments SIPROTEC objects object no. Output channel E3 (UsrSC10) Continuous output without restauration, – 1 relay, 1-pole Output channel E3 (UsrSC10) 2.1.3 Internal commands • Ref. to chap. 1.5.2 and 1.5.3 for additional notes regarding "Control mode REMOTE" and "Changing the setting group".
Page 27
Standard mapping 2-1 Offset Designation of the Internal Comments SIPROTEC objects object no. CFC-Incoming annunciation 2 (UsCfcSpI2) OFF Tagging ON/OFF, released as CFC input – CFC-Incoming annunciation 2 (UsCfcSpI2) ON CFC-Incoming annunciation 3 (UsCfcSpI3) OFF Tagging ON/OFF, released as CFC input –...
Standard mapping 2-1 2.2.1.8 Directional time overcurrent protection Offset Designation of the Comments Internal SIPROTEC objects object no. Phase A forward 1 = Phase A forward 2628 Phase B forward 1 = Phase B forward 2629 Phase C forward 1 = Phase C forward 2630 Phase A reverse 1 = Phase A reverse...
Standard mapping 2-1 2.2.2 Measured values • Ref. to chap. 1.3.2 for additional notes regarding scaling of measured values. 2.2.2.1 Recorded measured values Offset Designation of the Comments Scaling Internal SIPROTEC objects (32767 corresponds to ...) object no. Ia = 3276.7 A Ib = 3276.7 A...
Standard mapping 2-2 Offset Designation of the Internal Comments SIPROTEC objects object no. Output channel E3 (UsrSC10) Continuous output without restauration, – 1 relay, 1-pole Output channel E3 (UsrSC10) 3.1.3 Internal commands • Ref. to chap. 1.5.2 and 1.5.3 for additional notes regarding "Control mode REMOTE" and "Changing the setting group".
Page 39
Standard mapping 2-2 Offset Designation of the Internal Comments SIPROTEC objects object no. CFC-Incoming annunciation 2 (UsCfcSpI2) OFF Tagging ON/OFF, released as CFC input – CFC-Incoming annunciation 2 (UsCfcSpI2) ON CFC-Incoming annunciation 3 (UsCfcSpI3) OFF Tagging ON/OFF, released as CFC input –...
Standard mapping 2-2 3.2.1.18 Status annunciations • Ref. to chap. 1.5.7 for additional notes regarding "Stop data transmission". Offset Designation of the Comments Internal SIPROTEC objects object no. 14/0 >No Volt 1 = Binary input “No voltage (fuse blown)" is active –...
Standard mapping 2-2 3.2.2 Measured values • Ref. to chap. 1.3.2 for additional notes regarding scaling of measured values. 3.2.2.1 Recorded measured values Offset Designation of the Comments Scaling Internal SIPROTEC objects (32767 corresponds to ...) object no. Ia = 3276.7 A Ib = 3276.7 A...
Page 49
Standard mapping 2-3 Offset Designation of the Internal Comments SIPROTEC objects object no. CFC-Incoming annunciation 6 (UsCfcSpI6) OFF Tagging ON/OFF, released as CFC input – CFC-Incoming annunciation 6 (UsCfcSpI6) ON CFC-Incoming annunciation 7 (UsCfcSpI7) OFF Tagging ON/OFF, released as CFC input –...
Standard mapping 2-3 4.2.1.5 Diagnosis • Ref. to chap. 1.5.5 and 1.5.6 for additional notes regarding "Error with a summary alarm" and "Alarm summary event". Offset Designation of the Comments Internal SIPROTEC objects object no. Device OK 1 = Update of the device replica in the SIPROTEC device completed after initial start or restart <reserved>...
Standard mapping 2-3 4.2.1.8 Status annunciations • Ref. to chap. 1.5.7 for additional notes regarding "Stop data transmission". Offset Designation of the Comments Internal SIPROTEC objects object no. >No Volt 1 = Binary input “No voltage (fuse blown)" is active –...
Standard mapping 2-3 4.2.2 Measured values • Ref. to chap. 1.3.2 for additional notes regarding scaling of measured values. 4.2.2.1 Recorded measured values Offset Designation of the Comments Scaling Internal SIPROTEC objects (32767 corresponds to ...) object no. Ia = 3276.7 A Ib = 3276.7 A...
Standard mapping 2-3 4.2.3 Metered measurands • Ref. to chap. 1.3.3 for additional notes regarding scaling of metered measurands. Offset Designation of the Comments Scaling Internal SIPROTEC objects -1 of the unsigned long- object no. value corresponds to ...) Wp(puls) = Pulsed Energy Wp (active) -1 impulses (metering impulses at binary input)
Page 56
Standard mapping 2-3 7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping 4-10 C53000-L1840-B006-02...
Standard mapping 2-4 5.1.4 Application logic CFC • Ref. to chap. 1.5.4 and 1.6 for additional notes. Offset Designation of the Comments Internal SIPROTEC objects object no. CFC-Incoming annunciation 1 (UsCfcSpI1) OFF Tagging ON/OFF, released as CFC input – CFC-Incoming annunciation 1 (UsCfcSpI1) ON CFC-Incoming annunciation 2 (UsCfcSpI2) OFF...
PROFIBUS Nutzerorganisation PROFIBUS - Decentralized Peripherals PROFIBUS-DP PROFIBUS interface module with (electrical) isolated RS485 interface for the SIPROTEC devices from Siemens. PROFIBUS interface module with optical interface for the SIPROTEC devices from Siemens. Single Command Single-point Indication 7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping...