5.5
Inrush currents at power-on of main circuit and
control circuit
A molded-case circuit breaker and magnetic contactor may fail or malfunction due to an inrush current flowing through the
servo amplifier's power lines (input lines) at power on. Therefore, use products with the specifications described on the
following page.
Page 219 Molded-case circuit breakers, fuses, magnetic contactors
When circuit protectors are used, it is recommended that the inertia delay type, which is not tripped by an inrush current, be
used.
200 V class [G] [A]
The following shows the inrush currents (reference data) that will flow when 240 V AC is applied. Even when a 1-phase 200 V
AC power supply is used with MR-J5-10_ to MR-J5-200_, the inrush currents of the main circuit power supply will be the
same.
Servo amplifier
MR-J5-10_
MR-J5-20_
MR-J5-40_
MR-J5-60_
MR-J5-70_
MR-J5-100_
MR-J5-200_
MR-J5-350_
MR-J5-500_
MR-J5-700_
200 V class [WG]
The following shows the inrush currents (reference data) that will flow when 240 V AC is applied.
Servo amplifier
MR-J5W2-22G_
MR-J5W2-44G_
MR-J5W2-77G_
MR-J5W2-1010G_
MR-J5W3-222G_
MR-J5W3-444G_
400 V class [G] [A]
Servo amplifier
MR-J5-60_4_
MR-J5-100_4_
MR-J5-200_4_
MR-J5-350_4_
5 CHARACTERISTICS
168
5.5 Inrush currents at power-on of main circuit and control circuit
Inrush currents (A
)
0-P
Main circuit power supply (L1/L2/L3)
17 A (attenuated to approx. 3 A in 20 ms)
17 A (attenuated to approx. 7 A in 20 ms)
24 A (attenuated to approx. 11 A in 20 ms)
85 A (attenuated to approx. 10 A in 20 ms)
42 A (attenuated to approx. 20 A in 20 ms)
85 A (attenuated to approx. 20 A in 30 ms)
Inrush currents (A
)
0-P
Main circuit power supply (L1/L2)
23 A (attenuated to approx. 9 A in 20 ms)
36 A (attenuated to approx. 13 A in 20 ms)
23 A (attenuated to approx. 6 A in 20 ms)
Inrush currents (A
)
0-P
Main circuit power supply (L1/L2/L3)
21 A (attenuated to approx. 4 A in 10 ms)
26 A (attenuated to approx. 10 A in 10 ms)
78 A (attenuated to approx. 10 A in 10 ms)
Control circuit power supply (L11/L21)
20 A to 30 A (attenuated to approx. 1 A in 20 ms)
34 A (attenuated to approx. 2 A in 20 ms)
Control circuit power supply (L11/L21)
20 A to 35 A (attenuated to approx. 3 A in 20 ms)
Control circuit power supply (L11/L21)
40 A to 50 A (attenuated to approx. 0 A in 20 ms)