■Data set type homing
Move the machine to the position where the home position is to be set by performing the manual operation such as JOG
operation. When CR is on for longer than 20 ms, the stop position is stored into the non-volatile memory as the home position
absolute position data.
CR during servo-on should be turned on after checking that INP has turned on. If this condition is not satisfied, [AL. 096 Home
position setting warning] occurs. If homing is performed correctly, the alarm is automatically canceled.
The number of homing times is limited to 100000.
Homing can be performed during the servo-off.
Servo motor
INP (In-position)
CR (Home position setting)
ABSB0 (ABS transmission data bit 0)
ABSB1 (ABS transmission data bit 1)
ABSV (Absolute position undetermined)
Control circuit power supply
7 ABSOLUTE POSITION DETECTION SYSTEM
310
7.3 Absolute position detection system by DIO [A]
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Manual feeding with JOG
operation or others
20 ms or more