Alternative solutions with AS 620 B (1)
Function modules (FUM) and/or Signal modules (SIM)
I&C room
I&C room
Interfacing to the process takes place via I/O modules to which the I/O
comprising measurement transmitters and actuators are connected. Two module
types are available in AS620 to support a central or a distributed configuration:
•
FUM modules (function modules) for central configurations
•
SIM modules (signal modules) for distributed configurations
FUM modules
FUM modules have been specially developed for power plant applications. Within
the context of the higher I&C levels, the FUMs are equipped with preprocessing
units with medium to high processing performance.
The most important FUM tasks are:
•
Signal acquisition, conditioning, processing, monitoring, and sensor supply
•
Individual open and closed-loop controls
•
Time tagging with 1 ms resolution for events (both analog and binary)
FUM modules are inserted into sub-racks that are mounted in electronics
cabinets and are linked to the AP via the cabinet bus
2
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
FUM - Configuration
FUM - Configuration
AP
FUM
FUM
AP
FUM
FUM
JB
JB
JB
JB
M
Centralized
Centralized
Training Center
SIM - Configuration
SIM - Configuration
AP
AP
I&C room
I&C room
Profibus
Profibus
Field
Field
Field
SIM B
SIM B
SIM B
SIM B
M
Distributed
Distributed
TXP-CLC Course