Contents 11. Precautions ............................1-1 Installing the air conditioner ......................1-2 Power supply and circuit breaker ....................1-3 During operation ..........................1-4 Disposing of the unit ........................1-5 Others ..............................12. Product Specifications ....................... 2-1 The Feature of Product ........................
More than 2 indoor units should be installed when you use Free Joint Multi air conditioner. RJ060F3HXEA/RJ070F4HXEA - **024** indoor units cannot be connected. RJ050F2HXEA - **024**/MH052FMEA/MH052FUEA indoor units cannot be connected. RJ040F2HXEA - **052**/MH***FM*A/NJ***LHXEA/**18**/**24** indoor unites cannot be con- nected. 1-2 Power supply and circuit breaker If the power cord of the air conditioner is damaged, it must be replaced by the manufacturer or a qualified person in order to avoid a hazard.
- Release the valve caps on High and Low pressure side. - Use Lwrench to close the valve on the high pressure side. - Approximately 2 minutes after, close the valve on the low pressure side. - Stop operation of the air conditioner.- Disconnect the pipes. Samsung Electronics...
■ Space saving & Environmental Friendly ■ Reliability ■ Smart & Low Noise outdoor units in any condition Double layered felt structure absorbs noise by two times and felt is also covering top of the compressor to reduce the noise even more. Samsung Electronics...
ø18, 535 Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan Resin /steel Blower Type Resin/steel Resin/steel Resin/steel Motor Rated Output 2ROW 16STEP Heat Exchanger 2ROW 10STEP 2ROW 14STEP 2ROW 14STEP Refrigerant Control Unit Samsung Electronics...
Page 7
Drain Hose ø,mm ø18, 550 ø18, 550 ø18, 920 Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Blower Type Resin/steel Resin/steel Resin/steel Motor Rated Output Heat Exchanger 2ROW 14STEP 2ROW 14STEP 2ROW 16STEP Refrigerant Control Unit Samsung Electronics...
Page 8
ø18,550 ø18,550 ø18,550 Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan Blower Type Resin/steel Resin/steel Resin/steel Resin/steel Motor Rated Output Heat Exchanger 2ROW 10STEP 2ROW 10STEP 2ROW 10STEP 2ROW 16STEP Refrigerant Control Unit Samsung Electronics...
Page 9
Ø18,550 Ø18,550 Ø18,550 Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan Blower Type Resin/steel Resin/steel Resin/steel Resin/steel Motor Rated Output Heat Exchanger 2ROW 14STEP 2ROW 14STEP 2ROW 14STEP 2ROW 16STEP Refrigerant Control Unit Samsung Electronics...
Page 10
ø6.35x7.5 ø6.35x7.5 Refrigerant Pipe Size mmxL(m) ø9.52x7.5 ø9.52x7.5 Drain Hose ø,mm VP20(ID20/OD25) VP20(ID20/OD25) Type Cross Flow Fan Cross Flow Fan Blower Type Feedback SSR Feedback SSR Motor Rated Output Heat Exchanger 2ROW 12STEP 2ROW 12STEP Refrigerant Control Unit Samsung Electronics...
Page 11
Refrigerant Pipe Size mmxL(m) ø9.52x7.5 ø9.52x7.5 ø12.7x7.5 Drain Hose ø,mm VP20(ID20/OD25) VP20(ID20/OD25) VP20(ID20/OD25) Type Turbo Fan Turbo Fan Turbo Fan Blower Type steel steel steel Motor Rated Output Heat Exchanger 2ROW 20STEP 2ROW 20STEP 2ROW 20STEP Refrigerant Control Unit Samsung Electronics...
Remark DB97-02851C FNEA except MH052FNEA) Installation Plate (Plate-Hanger) DB90-02738A (MH052FNEA) Remote Control DB93-03170Z Indoor Batteries for Remote Control DB47-90024A Unit User Manual DB98-28925A Installation Manual DB98-31791A The design and shape can be changed according to the model. Samsung Electronics 2-25...
Page 30
Remark DB70-00819A FBEA except Installation Plate MH052FBEA) (Plate-Hanger) DB90-03483A (MH052FBEA) Remote Control DB93-04700S Indoor Batteries for Remote Control DB47-90024A Unit User Manual DB98-29019A Installation Manual DB98-31788A The design and shape can be changed according to the model. 2-26 Samsung Electronics...
Page 31
Remote Control DB93-04700S Batteries for Remote Control DB47-90024A Indoor Unit User Manual DB98-31994A Installation Manual DB98-31789A DB39-00943D C/W COMM2 Wired Remote Controller cables DB39-01047A Connect Wire The design and shape can be changed according to the model. Samsung Electronics 2-27...
Page 32
DB98-31790A The design and shape can be changed according to the model. Filter Image Part name Code-No. Remark DB63-02129C(Left) Pre-filter wash in waer DB63-02130C(Right) Catechin Filter DB63-00615B Clean with vaccum cleaner or soft bursh Deodorizing filter DB63-00616A 2-28 Samsung Electronics...
Page 33
Insulation cover band DB72-00109J Installation Manual DB98-27682A Indoor Unit Flexible hose DB94-01258C (Ass'y drain hose joint) Insulation drain hose DB62-04783A Rubber DB63-00237A (Grommet Hanger) Insulation hose DB72-00398B The design and shape can be changed according to the model. Samsung Electronics 2-29...
Page 34
Insulation-Install inlet DB72-00143E (MH052FMEA) Indoor Unit Insulation-drain DB72-00143G (MH052FMEA only) Cable-tie DB65-00191A Ass'y drain hose DB94-01270D M4x12 tapped Screw 6002-000213 Installation manual DB98-27682A Safety net DB63-01372A The design and shape can be changed according to the model. 2-30 Samsung Electronics...
Page 36
DB94-00758B Rubber DB63-00237A (Grommet Hanger) Indoor Unit Insulation-Drain Out DB62-03439N Insulation-Out DB62-03439J Insulation-Drain In DB62-03440N Cable-tie DB65-10088C Drain Pipe Holder DB90-02064A Wired remote controller Box DB97-01904G The design and shape can be changed according to the model. 2-32 Samsung Electronics...
Page 39
Ass'y -Label Kyoto Protocol DB98-28756A ) kg ) kg ) kg (RJ050F2HXEA) (RJ060F3HXEA) Nipple Connector DB67-00789A (RJ070/080F4HXEA) DB60-30010D Flare Nuts 5/8” Nipple Connector 1/2” to 5/8” DB67-01157A (Only RJ080F4HXEA) The design and shape can be changed according to the model. Samsung Electronics 2-35...
Page 40
Rubber Leg DB73-20134A Outdoor Unit Installation Manual DB98-32978A Ass'y -Label Kyoto Protocol DB98-28788A ) kg ) kg ) kg Flare Nuts 3/8” DB96-16155A Flare Nuts 5/8” DB96-16155B The design and shape can be changed according to the model. 2-36 Samsung Electronics...
Page 41
Transmitter Power cable DB39-00378E (Wire Harness-DC Source) (MIM-B13) Transmitter communication cable DB39-00253B (Connect Wire-COM) (MIM-B13) Transmitter Case DB61-00450B (Case-Relay PCB Out) (MIM-B13) Cable-tie DB65-10088B DB98-25776A Installation Manual (MIM-B13) The design and shape can be changed according to the model. Samsung Electronics 2-37...
(Use +Screw Driver.) 3) Loosen each 7 screws(CCW)on cabi front. (Use +Screw Driver.) 4) Loosen 2 screw(CCW)fixed to assemble Plate Control Out with Cabinet-Side RH. (Use +Screw Driver.) 5) Loosen 2 fixing screws(CCW)on Cabinet-Side RH. (Use +Screw Driver.) Samsung Electronics...
Page 44
Parts Procedure Remark 6) Loosen 4 screws(CCW)fixed to assemble Bracket Valve with Cabinet-Side RH. (Use +Screw Driver.) 7) Loosen 3 fixing screws(CCW)of Cabinet Side LF. (Use +Screw Driver.) Samsung Electronics...
Page 45
Ass’y Ass'y Control Out. Control Out 2) Detach several connectors from the PCB of Ass'y Control Out. 3) Detach 2 Connect Wires from Reactor. 4) Loosen 1 screw(CCW)fixed to assemble Ass'y Control Out with Partition. (Use +Screw Driver.) Samsung Electronics...
Page 46
2) Detach the Terminal Cover and detach the Connect Comp Wire from Compressor. 3) Disassemble the Felt Comp Sound. 4) Loosen the 3 bolts(CCW)at the bottom of Compressor like the picture on the right side. (Use Monkey Spanner.) Samsung Electronics...
Page 47
3) Loosen 2 fixing screws of the Ass'y Control Out. (Use +Screw Driver.) 4) Loosen 6 fixing screws and detach the Cabinet Upper. (Use +Screw Driver.) 5) Loosen 2 fixing screws, 7 bolts and detach the Cabinet Front. (Use +Screw Driver.) Samsung Electronics...
Page 48
Parts Procedure Remark 6) Loosen 2 fixing screw and pull up the Control Box. (Use +Screw Driver.) 7) Pull the felt and detach it. 8) Detach the Terminal Cover and detach the comp lead wire. Samsung Electronics...
Page 49
2) Disassemble the Inlet and Outlet Pipe by welding. Compressor 3) Loosen the fixing screw of the Heat Exchanger. (Use +Screw Driver.) 4) Detach the Heat Exchanger. 5) Loosen 3 nuts of the Compressor. (Use Monkey Spanner.) 6) Detach the Compressor. Samsung Electronics...
Cable miss-wiring Cable connection (Indoor & Outdoor unit) MPI error malfunction Cable connection (another indoor unit & The number of indoor unit mismatched outdoor unit), SW01(outdoor) Compressor discharge sensor error(Short/Open) Outdoor unit Outdoor unit error Outdoor unit (Error code) Samsung Electronics...
Page 58
Outdoor Unit Power Reset Indoor unit communication error Outdoor unit communication error Simultaneous operation error : On : Flickering : Off If you turn off the air conditioner when the LED is flickering, the LED is also turned off. Samsung Electronics...
Page 59
Error of float switch Error of setting option switches for optional accessories EEPROM error EEPROM option error : On : Flickering : Off If you turn off the air conditioner when the LED is flickering, the LED is also turned off. Samsung Electronics...
Page 60
Setting the outdoor unit capacity option error EEPROM error EEPROM option error MPI no feedback Error : On : Flickering : Off If you turn off the air conditioner when the LED is flickering, the LED is also turned off. Samsung Electronics...
Page 61
: Flickering : Off If you turn off the air conditioner when the LED is flickering, the LED is also turned off. If you re-operate the air conditioner, it operates normally at first, then detect an error again. Samsung Electronics...
Page 63
Compressor trip by OLP temperature control mode Over current Compressor Vlimit Error DC link Voltage error (under 150V, over 410V) Abnormal compressor running (Compressor Rotation Error) Current sensor error DC link Voltage sensor error OTP Error Inverter micom zero-crossing error Samsung Electronics...
Push the button to set the display panel to ➡ ➡ Every time you push the button, the display panel reads ➡ ➡ . . . ➡ ➡ ➡ ➡ ➡ ➡ repeatedly. Samsung Electronics...
Page 65
If all lamps of indoor unit are flickering, Plug out, plug in power plug again and press ON/OFF key to retry. If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is set up for its model. Samsung Electronics...
Page 66
Push the button to set the display panel to Setting is not required if you must Every time you push the button, the display panel reads a value which has a default..repeatedly. 4-10 Samsung Electronics...
Page 67
If all lamps of indoor unit are flickering, plug out, plug in power plug again and press the ON/OFF key to retry. If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is set up for its model. Samsung Electronics 4-11...
Page 68
Every time you push the button, the display panel reads ..repeatedly. Push the button to Push the button to set the display panel to Every time you push the button, the display panel reads ..repeatedly. 4-12 Samsung Electronics...
Page 69
If all lamps of indoor unit are flickering, Plug out, plug in power plug again and press ON/OFF key to retry. If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is set up for its model. Samsung Electronics 4-13...
Page 72
-200000-300000 -200000-300000 External Static Pressure 4.0(Standard) (mmAq) 012221-194247 012221-194360 012221-1943A2 012223-194105 MH052FUEA -200000-300000 -200000-300000 -200000-300000 -200000-300000 If you are going to use up to SEG 24, please refer to following instruction. SEG 18 : Not in use Change temperature display...
The compressor stops intermittently or the fan speed of the COOL mode or DRY mode, and fan speed of the indoor unit decreases to prevent inside/outside air frozen indoor unit decreases. depending on the inside/outside air temperature. Samsung Electronics 4-17...
Total capacity of the indoor units Fan RPM (H:high,L:low,Blank:off ) Safety control Safety control The EEV 2 and EEV 3 of MH040FXEA2B/MH040FXEA2C/MH050FXEA2B/MH050FXEA2C/MH18VF1X/ MH19VF1X models are always displayed as blank. The EEV 3 of MH060FXEA3B model is always displayed as blank. 4-18 Samsung Electronics...
Page 75
Push [K1 ] button on the display PCB of outdoor unit once, then begins to start “Pipe check operation” with displaying as below.2. Button [K1] 1 times DIS 01 DIS 02 Display [DIS 01 ] is flickering on the setting time. Outdoor Temperature or more less than Time duration (Cool mode) (Heat mode) 5min~10min 20min~50min Samsung Electronics 4-19...
Page 76
- On this mode the controller will ignore the manual address number set on the rotary switch on the indoor PCB. - To confirm the indoor address number assigned by this mode, use "TEST MODE" and the address number will be displayed on the LED display on the indoor unit. 4-20 Samsung Electronics...
Page 77
02--communication with indoor unit C; 03--communication with indoor unit D; In case of Manual address mode,you can do pipe check operation for check whether you connect the pipes correctly or not. But you need set indoor address switch yourselves. Samsung Electronics 4-21...
Page 79
INSTALLATION TEST MODE (with all indoor units functioning) Please do cool mode try-run or heat mode try run. Cool mode try-run :Push the [K2 ] button three times. Heat mode try-run :Push the [K2 ] button once. Samsung Electronics 4-23...
Page 80
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details No RMC address Indication and Details RMC1 RMC2 address setting mode ※ You must set RMC address setting mode when using the centralized Control . 4-24 Samsung Electronics...
Page 81
Indoor unit heat exchanger in temperature sensor error (open/short) E237 Condenser temperature sensor error (open/short) E251 Compressor Discharge temperature sensor error (open/short) E251 Compressor OLP sensor error (open/short) E320 Please, The System turn off and replace sensor which is related. Guidance Samsung Electronics 4-25...
Page 82
Replace outdoor unit’s ass’y control or indoor unit’s Step 2 EEV Coil ass’y control. Basically, This error caused by communication between Indoor Units and Outdoor Unit. Guidance First of all, check the all communication connection and PCB’s status. 4-26 Samsung Electronics...
Page 83
This is caused by protection mode behavior. Analysis This is indoor Evaporator Freezing protection mode. Please, check indoor unit, whether inlet or outlet grill is closed. Step 1 Step 2 Please, check indoor unit, whether indoor fan is working. Samsung Electronics 4-27...
Page 84
Error code. Check point Remarks These Error codes only apply with Try-run mode, in case of system have some defect as result of try-run operation. Analysis Refer to self-detection algorithm (Check Error Code meaning and check it out) 4-28 Samsung Electronics...
Page 89
DC 4.75V - 5.25V refer to picture Main control 3.3V refer to picture DC 3.0V - 3.6V 4. Checking PFCM Check Resistance between R and S RJ040F2HXEA/RJ050F2HXEA RJ060F3HXEA/RJ070F4HXEA/RJ080F4HXEA RJ100F5HXEA Measuring point Normal value Resistance R - S over the hundreds Samsung Electronics 4-33...
Page 93
Press K4 key on the outdoor display PCB for several time to change the display to sensor temperature value. Left 1 digit of the LED is data index and Right 2 digits are the value. Index Value Remark Discharge sensor temperature OLP sensor temperature The unit is degree C Condenser sensor temperature Outdoor sensor temperature Samsung Electronics 4-37...
Page 94
Left 1 digit of the LED is data index and Right 3 digits is the value. Index Value Remark EEV-A step EEV-B step The step value range is EEV-C step RJ040/050F2HXEA between Zero and 480. RJ060F3HXEA /RJ70/080F4HXEA EEV-D step 4-38 Samsung Electronics...
The parts should be replaced in the following procedure. Check for any faulty part. Detach the faulty part. Replace it with a new part. Set an address. Check the operation of the new part. The repair is completed. Samsung Electronics 4-39...
Page 119
PLATE STEEL SGCC-M,T0.8 DB63-01999A GUARD TOP OUTLET HSWR,Ø1.5 DB61-03554A BRACKET MOTOR SGCC-M,T2.0 DB70-00921A PLATE MOTOR SGCC-M,T1.0 DB31-00517A MOTOR FAN SIC-55CV-F137-1,SIBAURA DB93-06165B ASS'Y CONTROL IN ASS'Y DB93-06165F ASS'Y CONTROL IN ASS'Y 35-1 DB90-03842A ASS'Y CASE CONTROL PD ASS'Y 5-24 Samsung Electronics...
Page 120
ABS V0,T2.5 35-8 DB93-07023B ASS'Y PCB MAIN IN DB93-07023E ASS'Y PCB MAIN IN 35-9 DB65-00004U TERMINAL BLOCK 35-10 DB61-40291C HOLDER WIRE 35-11 DB63-02001A COVER CONTROL SGCC-M,T0.5 35-12 DB61-03550A CASE PCB ADDRESS ABS V0,T2.5 35-13 DB93-04640C ASS'Y PCB SUB Samsung Electronics 5-25...
Page 137
6. PCB Diagram 6-1. INDOOR PCB Diagram FNEA (MAIN PCB) The red number connecter is not used. Power Temperature Sensor Motor RPM Feedback Auto Grill Remocon Module HVPS(High voltage Generator) Humidity Sensor BLADE-H Step Motor Anions Display Indoor Fan Motor Samsung Electronics...
Page 138
#2:Motor driving signal output_1 #2:MPI driving signal output (+) #3:Motor driving signal output_2 #3:Motor driving signal output_2 #3:DV12V #4:Motor driving signal output_3 #4:Motor driving signal output_3 #4:MPI feedback signal input #5:Motor driving signal output_4 #5:Motor driving signal output_4 Samsung Electronics...
Page 140
The red number connecter is not used. Motor Rpm FeedBack Melody ROOM/EVA IN Download Connector EVE OUT COM1 Indoor Fan Motor COM2 POWER SUB PCB Connection Blade Step Motor Module PCB Connection Auto Grille Step Motor 1 Display PCB Connection Auto Grill Step Motor2 Samsung Electronics...
Page 141
FNEA/MH FBEA/MH FVEA/MH FAEA/MH FJEA (SUB PCB) The red number connecter is not used. External Signal MAIN PCB Connection Samsung Electronics...
Page 142
TEMPRATURE SENSOR 5 CN44 FAN MOTOR FEEDBACK 6 CN61 STEP MOTOR 7 CN71 POWER IN 8 CN72 FAN MOTOR 9 CN81 MPI /SPI 10 CN91 DISPLAY 11 CN62 STEP MOTOR(AUTO GRILL) 12 CN63 STEP MOTOR 13 CN42 HUM-SENSOR Samsung Electronics...
Page 143
CN41-Temp. sensor CN51-FLOAT S/W CN61, CN62-Slide Panel CN83- External Control #1:ROOM Temp. Sensor #1:GND #1,#6:DC12V #1:On/off Contact point input #2:GND #2:Float S/W #2~#5:Motor Control #2:GND #3:EVA IN Temp. sensor #7~#10:Not used #4:GND CN42-Temp. sensor #1:EVA OUT Temp. Sensor #2:GND Samsung Electronics...
Page 144
FSEA (cont.) - Panel CN01 : Connect the Main PBA of the Indoor Unit #1~#5:Control Display LED #6:Not used connection #7:Receive signals from wireless remote controller Connector #8:GND #9:VCC (DC5V) Samsung Electronics...
Page 145
DC12V Out(Wired Remocon Power) : YW396-02V(WHT) Panel Louver(Stepping Motor) : SMW250-10(WHT) Micom Program Download : SMW200-10(BLK) External Control Out(Error, Compressor State) : SMW250-04(RED) Display PCB : SMW200-9(WHT) External Control In(On/Off Control Signal) : SMW250-02(RED) SSR Fan Control : SMW250-03(WHT) Samsung Electronics...
Page 146
#2~#5. Control SIGNAL #2~#5.Communication Signal #1. Communication Signal F1 #1.Communication Signal F1 #2. Communication Signal F2 #2.Communication Signal F2 CN20-MICOM Download2 CN10-MICOM Download1 > For Developer,Not for field >For Developer, Not for field > 7pin Downloader >10pin Downloader 6-10 Samsung Electronics...
Page 147
Address Switch Heater Temperature Option Switch Wired Remote Controller Power(12V) Fan (Tap Control) Control Signal Ventilator Drain Pump Display Hot Coil Operating Check Signal Fan (SSR) HALL IC Trans In Download Main Power COM 1 Trans out Samsung Electronics 6-11...
Page 148
#4 : DC 15V #5 : FAN RPM #6 : FAN RPM feedback CN13-MICOM DOWN CN451-COMP Cn051-REACTOR CN301-COMM #1~#10 MICOM DOWN #1 W phase #1~#2 : REACTOR #1 : COM1 #2 V phase #2 : COM2 (inverter micom) 6-12 Samsung Electronics...
Page 149
#1 5V #1 DC12V #3~#4 EVA OUT B #5 DC 12V #2~#5 Sensor #2 GND #5~#6 EVA IN C #6~#9 EEV B signal #7~#8 EVA IN D #11~#14 Grid1~4 #15~#21 Segmanet7~1 #22~#25 Kin4~1 #27 Gnd #28 12V Samsung Electronics 6-13...
Page 150
RJ060F3HXEA/RJ070F4HXEA/RJ080F4HXEA MAIN PCB 13 14 6-14 Samsung Electronics...
Page 151
RJ060F3HXEA/RJ070F4HXEA/RJ080F4HXEA SUB PCB Samsung Electronics 6-15...
Page 152
#6 INV. SMPS signal CN31 - COMM CN33-Sub Comm CN37-MICOM DOWN CN35- AS PROM #1 : COM1 #1 DC12V #1~#10 MICOM DOWN #1~#7 MICOM DOWN #2 : COM2 #2 GND (AS PRO USING) #3 DC5V #4 COM1 #5 COM2 6-16 Samsung Electronics...
Page 153
6 4 7 5 ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ Samsung Electronics 6-17...
Page 154
CN52 EVA OUT SENSOR CN83-EEV D CN84-EEV E #1~#2 EVA OUT A #1~#4 EEV signal #1~#4 EEV signal #3~#4 EVA OUT B #5 DC 12V #5 DC 12V #5~#6 EVA OUT C #7~#8 EVA OUT D #9~#10 EVA OUT E 6-18 Samsung Electronics...
8. Schematic Diagram 8-1 INDOOR UNIT FNEA/MH FVEA This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 171
FBEA This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 172
FAEA This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 173
FSEA This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 174
FMEA This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 175
FJEA This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 176
LHXEA/MH FUEA This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 177
This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 178
This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 179
8-2 OUTDOOR UNIT RJ040F2HXEA/RJ050F2HXEA (PCB MAIN) This Document can not be used without Samsung's authorization. 8-10 Samsung Electronics...
Page 180
RJ040F2HXEA/RJ050F2HXEA (PCB SUB) This Document can not be used without Samsung's authorization. Samsung Electronics 8-11...
Page 181
RJ060F3HXEA/RJ070F4HXEA/RJ080F4HXEA (PCB MAIN) This Document can not be used without Samsung's authorization. 8-12 Samsung Electronics...
Page 182
RJ060F3HXEA/RJ070F4HXEA/RJ080F4HXEA (PCB SUB) This Document can not be used without Samsung's authorization. Samsung Electronics 8-13...
Page 183
RJ100F5HXEA (MAIN PCB) This Document can not be used without Samsung's authorization. 8-14 Samsung Electronics...
Page 184
This Document can not be used without Samsung's authorization. Samsung Electronics 8-15...
Page 185
RJ100F5HXEA (EMI PCB) This Document can not be used without Samsung's authorization. 8-16 Samsung Electronics...
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines), salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice. Samsung Electronics...
2. Make sure that you put the remote control unit in an area not exposed to direct sunlight, and where there is no source of heat. 3. Make sure that you use the remote control unit in an area away from TVs, audio units, cordless phones, fluorescent lighting Samsung Electronics...
Page 188
183kgf cm with a torque wrench. Service port 7. Check for gas leakage. At this time, especially check for gas leakage from the 3 way valve’s stem nuts, and from the service port cap. Samsung Electronics...
Page 189
183kgf cm with a torque wrench. 7 Check for gas leakage. Valve stem - At this time,especially check for gas leakage from the 3-way valve ’s stem nuts,and from the service port cap. Stem cap Service port Samsung Electronics...
Page 190
RJ080F4HXEA RJ100F5HXEA pressure valve. 7) Stop operation of the air conditioner. 8) Close the 3 way valve, disconnect the pressure gauge, and open the 3 way valve again. 9) Close the cap of each valve. Samsung Electronics...
Page 191
9-5 Flare Nut Fixing Torque Torque (kg . cm) Torque(kg . cm) Outer diameter Fixing Torque Final Torque ø 6.35 mm (Liquid Side) ø 9.52 mm (Gas Side) ø 12.7 mm (Gas Side) Samsung Electronics...
Page 192
6. Make sure you do not bend the connection pipes in the middle and store together with the cables. 7. Move the indoor and outdoor units to a new location. 8. Remove the mounting plate for the indoor unit and move it to a new location. Samsung Electronics...
Page 193
KW/BTU’ Liter Floor 220V, 60Hz 208~230V, 60Hz Mont blanc 200~220V, 50Hz Vivace Neo-forte 220~240V, 50Hz (EEV ) 208~230V, 60Hz, 3~ Neo-forte 380~415V, 50Hz, 3~ Korea 127V, 50Hz Crystal 380V, 60Hz, 3~ Hydro Unit 460V, 60Hz, 3~ HYDRO Water tank Samsung Electronics...
Page 195
1 ~ 9 KOREA 2 WAY DVM M INI A ~ Z EXPORT M INI 4 WAY (7) Refrigerant DVM HOM E 4 WAY WDVM R410A X DUCT ECO Heating (Slim) Unitary (Ducted Split) (CCD) Unitary (RoofTop) 9-10 Samsung Electronics...
Page 199
Heat exchanger; A device, used to transfer heat from a fluid on one side of a barrier to a fluid ASS’Y EVAP/ASS’Y COND on the other side without bringing the fluids into direct contact. (Full name : assemble evaporator / assemble condenser) 9-14 Samsung Electronics...
Page 200
It occurs when the drain pump is plugged out or it is out of order. Check the power of the drain pump and the position of the drain hose, and when the pump is faulty, contact the drain pump manufacturer. Samsung Electronics do not manufacture drain pumps. So, we are not able to correct the drain pump problems.
Page 201
Set up a sun blind over the outdoor unit and clear the neighboring obstacles from the outdoor unit to provide good ventilation. When it goes off frequently during a heat wave, it would prevent the turn-off and increase the cooling capacity cleaning the outdoor unit or spraying some water to the heat exchanger. 9-16 Samsung Electronics...
Page 202
There is a cost table. But, our service engineer needs to visit to total up the cost correctly. When you move in, make sure to contact Samsung Electronics Service Center or Authorized Service Agent in advance to streamline the process.
Page 203
But generally the value of fresh indoor temperature is that below 0.2(m/s) of indoor air circulation, the temperature is 21~28 C when the wall temperature is the same as the indoor's and relative humidity is 30~31% in summer, the winter temperature is 20~24 C and relative humidity is 30~60% in winter. 9-18 Samsung Electronics...