Alarm status flag
■Device No.
Name
Alarm status flag
■Description
This signal turns on when an alarm occurs. For details on the alarms, refer to the following.
Page 142 Latest alarm code storage area
Page 143 Latest alarm ID storage area
■Turning off Alarm status flag
After eliminating the cause of the alarm, Alarm status flag (RX6) remains on until either of the following operations is
performed.
• Turning off and on the NZ2AW1GNAL or executing the remote reset
• Turn on and off Error reset request flag (RY0).
AnyWireASLINK version compatibility inspection error flag
■Device No.
Name
AnyWireASLINK version compatibility inspection error flag
■Description
This signal turns on when an error is detected in the AnyWireASLINK version compatibility inspection.
■Turning off AnyWireASLINK version compatibility inspection error
To turn off AnyWireASLINK version compatibility inspection error flag (RX8), eliminate the cause of the error and perform
either of the following operations.
Until then, AnyWireASLINK version compatibility inspection error (RX8) remains on.
• Turn off and on the NZ2AW1GNAL or execute the remote reset.
• Turn on and off Error reset request flag (RY0).
• Turn off and on AnyWireASLINK version compatibility inspection command (RYD).
Device No.
RX6
Device No.
RX8
Appendix 1 Remote I/O Signals
A
APPX
131