Number of word data points setting per frame
■Address
Name
Word data points setting per frame
■Description
Set the number of points to be stored in one frame of AnyWireASLINK transmission frame.
The word data use setting and the relationship between setting and setting value are as follows.
Setting
Not use
2 words (input 1 word, output 1 word)
4 words (input 2 words, output 2 words)
8 words (input 4 words, output 4 words)
16 words (input 8 words, output 8 words)
32 words (input 16 words, output 16 words)
If Word data use setting (address: 0101H) is 0000H (Not use), set this setting to 0000H (Not use) also.
The settings that can be set differ depending on the word data use setting. The number of word points that exceeds the word
points setting cannot be set.
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Number of word
data points per frame setting range error (error code: 1805H) is displayed. Also, the setting will not be reflected in the non-
volatile memory.
If Module parameter reflection request flag (RYC) is turned on after writing a combination other than the one that can be set,
Word data setting combination error (error code: 180DH) is displayed. Also, the setting will not be reflected in the non-volatile
memory.
The combinations that can be set are the same as those for the word data use setting.
Page 151 Word data use setting
Startup operating mode setting
■Address
Name
Startup operating mode setting
■Description
Set whether to acquire slave module information at start-up.
The relationship between setting and setting value is as follows.
Setting
Without slave module information acquisition
With slave module information acquisition
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Startup operation
mode setting range error (error code: 1806H) is displayed. Also, the setting will not be reflected in the non-volatile memory.
Address
0105H
Setting value
0000H (initial value)
0001H
0002H
0003H
0004H
0005H
Address
0107H
Setting value
0000H (initial value)
0001H
Appendix 3 Remote Buffer Memory
A
APPX
153