Number of transmission points setting switch enable/disable status flag
■Device No.
Name
Number of transmission points setting switch enable/disable status flag
■Description
The status of number of transmission points of AnyWireASLINK setting switch can be checked.
• When enabled: ON
• When disabled: OFF
Even if the switch is changed after the module is started, because the module operation does not change, the
value of Number of transmission points setting switch enable/disable status flag (RX9) does not change and
the state at the time of module start-up is maintained.
If the number of points is set from the engineering tool when the number of transmission points of
AnyWireASLINK setting is enabled, an error will occur.
Module parameter reflection completion flag
■Device No.
Name
Module parameter reflection completion flag
■Description
When setting the module parameters from the program, Module parameter reflection request flag (RYC) turns on and this
signal turns on when the parameter data writing to the non-volatile memory is completed.
This signal automatically turns off when Module parameter reflection request flag (RYC) turns off.
AnyWireASLINK version compatibility inspection executing flag
■Device No.
Name
AnyWireASLINK version compatibility inspection executing flag
■Description
This signal turns on when the AnyWireASLINK version compatibility inspection is started.
■Turning off AnyWireASLINK version compatibility inspection executing flag
AnyWireASLINK version compatibility inspection executing flag (RXD) turns off when the following conditions are met.
• The AnyWireASLINK version compatibility inspection has completed.
• AnyWireASLINK version compatibility inspection command (RYD) is turned on and off.
APPX
132
Appendix 1 Remote I/O Signals
Device No.
RX9
Device No.
RXC
Device No.
RXD