Adjustment mode flag
■Device No.
Name
Adjustment mode flag
■Description
This flag turns on when the ASLINKMONITOR is in the adjustment mode.
■Turning off Adjustment mode flag
Adjustment mode flag (RXF) turns off when either of the following conditions is met.
• The ASLINKMONITOR is in the normal mode.
• The ASLINKMONITOR in the adjustment mode is disconnected.
For details on the adjustment mode, consult Anywire Corporation.
Slave module alarm signal
■Device No.
Name
Slave module alarm signal
■Description
This signal turns on when any of the following errors occurs.
• Slave module access error (alarm code: 0D2CH)
• Slave module access error (alarm code: 0D2DH)
• Parameter setting value error (alarm code: 0D2FH)
• Parameter access error (alarm code: 0D30H)
• Slave module status error (alarm code: 0D31H)
• Type mismatch error (alarm code: 0D80H)
• Slave module device version inconsistency error (alarm code: 0D81H)
• Compatibility inspection error (Parameter access error) (alarm code: 0D84H)
• Same ID used error (alarm code: 0D90H)
• No ID setting error (alarm code: 0D91H)
• 1024-point non-compatible slave module connection detection error (alarm code: 0DA0H)
■Turning off Slave module alarm signal
To turn off Slave module alarm signal (RX10), after eliminating the status error in the slave module or setting the address of
the slave module again, perform either of the following operations.
Until then, Slave module alarm signal (RX10) remains on.
• Turn off and on the NZ2AW1GNAL or execute the remote reset.
• Turn on and off Error reset request flag (RY0).
Device No.
RXF
Device No.
RX10
Appendix 1 Remote I/O Signals
A
APPX
133