Output data hold/clear setting
■Address
Name
Output data hold/clear setting
■Description
Set whether to clear or retain the output to the AnyWireASLINK slave module when the line from the CC-Link IE TSN is
disconnected and a stop error occurs in the CPU module.
The relationship between setting and setting value is as follows.
Setting
Clear output when error occurs
Hold output when error occurs
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Output data hold/
clear setting range error (error code: 180AH) is displayed. Also, the setting will not be reflected in the non-volatile memory.
Easy replacement setting for one slave module
■Address
Name
Easy replacement setting for one slave module
■Description
Enable or disable easy replacement setting for one slave module.
The relationship between setting and setting value is as follows.
Setting
Easy replacement enable for one slave module
Easy replacement disable for one slave module
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Easy replacement
setting for one slave module range error (error code: 180BH) is displayed. Also, the setting will not be reflected in the non-
volatile memory.
Bit transmission cycle time
■Address
Name
Bit transmission cycle time
■Description
These areas are for checking the bit transmission cycle time of AnyWireASLINK.
These areas store 32-bit integers. (Unit: 0.1ms, rounded up to the 2nd decimal point)
020AH (522)
Upper
For details on the calculation formula of the bit transmission cycle time, refer to the following.
Page 178 Transmission cycle time formula
APPX
156
Appendix 3 Remote Buffer Memory
Address
010BH
Setting value
0000H (initial value)
0001H
Address
010CH
Setting value
0000H (initial value)
0001H
Address
020AH to 020BH
020BH (523)
Lower