hit counter script

Mitsubishi Electric FR-A862 Instruction Manual page 27

Table of Contents

Advertisement

Terminal connection diagrams

A jumper is installed across terminal R1/L11 and terminal P/+, and across terminal S1/L21 and terminal N/-. When using a separate power
supply for the control circuit, remove the jumpers from R1/L11 and S1/L21.

The function of these terminals can be changed with the input terminal assignment (Pr.178 to Pr.189).

Terminal JOG is also used as the pulse train input terminal. Use Pr.291 to choose JOG or pulse.

The X10 signal (NC contact input specification) is assigned to terminal MRS in the initial setting. Set Pr.599 = "0" to change the input
specification of the X10 signal to NO contact.

Terminal input specifications can be changed by analog input specification switchover (Pr.73, Pr.267). To input a voltage (0 to 5 V/0 to 10 V), set
the voltage/current input switch OFF. To input a current (4 to 20 mA), set the voltage/current input switch ON. Terminals 10 and 2 are also used
as a PTC input terminal. (Pr.561)

It is recommended to use 2 W 1 k when the frequency setting signal is changed frequently.

The function of these terminals can be changed with the output terminal assignment (Pr.195, Pr.196).

The function of these terminals can be changed with the output terminal assignment (Pr.190 to Pr.194).

No function is assigned in the initial setting. Use Pr.192 for function assignment.
 Terminal FM can be used to output pulse trains as open collector output by setting Pr.291.
 Not required when calibrating the scale with the operation panel.
NOTE
• To prevent a malfunction due to noise, keep the signal cables 10 cm or more away from the power cables. Also, keep the
cables of the main circuit for input and output separated.
• After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take caution not to allow chips and other foreign matter to enter the
inverter.
• Set the voltage/current input switch correctly. Incorrect setting may cause a fault, failure or malfunction.
• Terminals S1, S2, SIC, So (SO), and SOC are for manufacturer setting. Do not remove the shorting wires across terminals S1
and PC, terminals S2 and PC, and terminals SIC and SD. When the shorting wires are removed, the inverter does not
operate.
Connection between the converter unit and the inverter
Perform wiring so that the commands sent from the converter unit are transmitted to the inverter without fail. Incorrect
connection may damage the converter unit and the inverter.
For the wiring length, refer to the table below.
Across terminals P and P and
Total wiring
terminals N and N
length
Other control signal cables
For the cable gauge of the cable across the main circuit terminals P/+ and N/- (P and P, N and N), refer to
MCCB
MC
Power
supply

Do not install an MCCB across terminals P/+ and N/- (across terminals P and P/+ or across N and N/-). Connecting the opposite polarity of
terminals N/- and P/+ will damage the inverter.

For the terminal used for the X10 signal input, set "10" in any of Pr.178 to Pr.189 (input terminal function selection) to assign the function.
(The X10 signal is assigned to terminal MRS in the initial setting.)
For the X10 signal, NC contact input specification is selected in the initial setting. Set Pr.599 = "0" to change the input specification to NO
contact.

For the terminal used for the X11 signal input, set "11" in any of Pr.178 to Pr.189 (input terminal function selection) to assign the function. For
RS-485 or any other communication where the start command is only transmitted once, use the X11 signal to save the operation mode at the
time of an instantaneous power failure.

Always connect terminal RDA of the converter unit and terminal MRS (X10) of the inverter, and terminal SE of the converter unit and terminal SD
(sink logic) of the inverter. Not connecting these terminals may damage the converter unit.
26
INSTALLATION AND WIRING
50 m or lower
30 m or lower
Converter unit
(FR-CC2)
∗1
R/L1
P/+
P/+
N/-
N/-
S/L2
R1/L11
S1/L21
T/L3
R1/L11
S1/L21
∗4
MRS(X10)
RDA
∗2
RDB
X11
IPF
RES
RSO
∗4
SD
SE
Inverter
U
V
M
W
∗3
page
29.

Advertisement

Table of Contents
loading

This manual is also suitable for:

800 seriesA800

Table of Contents