Grounding the Chassis
• Grounding lug—A two-holed standard barrel lug that supports up to 6 AWG wire. This lug is supplied
• Grounding screws—Two M4 x 8 mm (metric) pan-head screws. These screws are shipped with the
• Grounding wire—Not supplied with the accessory kit. This wire should be sized to meet local and
• Number 1 Phillips-head torque screwdriver.
• Crimping tool to crimp the grounding wire to the grounding lug.
• Wire-stripping tool to remove the insulation from the grounding wire.
Step 1
Use a wire-stripping tool to remove approximately 0.75 inch (19 mm) of the covering from the end of the grounding
wire.
Cisco Nexus 9504 NX-OS Mode Switch Hardware Installation Guide
22
with the accessory kit.
accessory kit.
national installation requirements. Depending on the power supply and system, a 12 AWG to 6 AWG
copper conductor is required for U.S. installations. We recommend that you use commercially available
6 AWG wire. The length of the grounding wire depends on the proximity of the switch to proper grounding
facilities.