BusAdapter BA 2xSCRJ

6.2 Connecting

6.2
Connecting
Installing the bus connector
Install the PROFINET connector according to the instructions in the PROFINET Installation
Guide (https://www.profibus.com/).
Tools required
3 to 3.5 mm screwdriver, alternatively TX10 (torx).
Accessories required
• Connector for PROFINET connection: IE SCRJ POF Plug
• Fiber-optic cable:
– IE POF standard cable (6XV1874-2A)
– IE POF trailing cable (6XV1874-2B)
– IE PCF standard cable (6XV1861-2A)
– IE PCF trailing cable (6XV1861-2C)
Requirements
• Prepare the IE POF cables with the connectors IE SCRJ POF Plug or IE SC RJ PCF Plug.
You will find more Instructions in the installation instructions:
– POF fiber-optic cables with IE SCRJ POF plugs (A5E00351141).
– PCF fiber-optic cables with IE SCRJ PCF plugs (A5E00835119).
• When installing the fiber-optic cable, make sure the bending radius is not less than
permitted:
– IE POF/PCF standard cable: 150 mm
– IE POF/PCF trailing cable: 60 mm
• The maximum lengths of the fiber-optic cables are as follows:
– IE POF standard cable: 50 m
– IE POF trailing cable: 50 m
– IE PCF standard cable: 100 m
– IE PCF trailing cable: 100 m
• When the PROFINET device is the last device of the fiber-optic cable network, the
unoccupied fiber-optic cable interface must be closed with a blanking plug. When the
modules ship, the blanking plugs are inserted in the PROFINET sockets of the BusAdapter.
28
Equipment Manual, 08/2020, A5E41449003-AB