Siemens 8DB10 Installation And Operating Instructions Manual page 195

Extendable fixed-mounted circuit-breaker switchgear up to 40.5 kv
Table of Contents

Advertisement

1
Initial situation
3
Switch the three-position disconnector to OPEN position (insert the
operating lever for the DISCONNECTING function and turn 180°
counter-clockwise).
5
Push the right-hand control gate to the left.
7
Remove the operating lever for the DISCONNECTING function.
The right-hand control gate returns to its initial position.
864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06
Decoupling the busbar section (system 1)
2
Push the left-hand control gate to the left.
4
Remove the operating lever for the DISCONNECTING function.
The left-hand control gate returns to its initial position.
6
Switch the three-position disconnector to OPEN position (insert the
operating lever for the DISCONNECTING function and turn
180° counter-clockwise).
Operation
195/214