Setting Of Error-Time Output Mode - Mitsubishi Electric QX10-TS User Manual

I/o module type building block
Table of Contents

Advertisement

1
GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q

1.3.2 Setting of error-time output mode

Set the error-time output mode on the I/O assignment tab of PLC parameter in GX
Developer.
Select "Output" or "I/O mix" in the "Type" combo box on the I/O assignment tab of PLC
parameter. Then, click the "Detailed setting" button, and then select "Clear" or "Hold" in
the "Error time output mode" combo box.
Choose Output/I/O mix.
Choose Detailed setting.
Choose Clear/Hold
(default: Clear).
1 - 20
1 - 20