SSA911.01TH
A6V11739247_en--_b
2021-09-03
Hindustan Hydraulics & Pneumatics, Chennai - 01.
Contact person : V. Anandha krishnan - 98409 21885
Wireless radiator valve actuator, works with RDS110.R
RF-controlled actuator communication based on THREAD protocol (2.4 GHz,
bidirectional)
Connection and operation with RDS110.R and optionally RCR114.1
Battery-powered by commercially available 1.5 V AA batteries
Valve thread connection M30x1.5 mm
Nominal stroke 2.5 mm
Valve positioning force 90 N
Automatic adaptation to valve
Integrated temperature sensor and PI controller
Phone : 2534 3066, 2534 5625, 2534 5587
E-Mail : hhp@hindustanhydraulic.in
Smart Infrastructure

Advertisement

loading

Summary of Contents for Siemens SSA911.01TH

  • Page 1 Smart valve actuator SSA911.01TH Wireless radiator valve actuator, works with RDS110.R RF-controlled actuator communication based on THREAD protocol (2.4 GHz, bidirectional) Connection and operation with RDS110.R and optionally RCR114.1 Battery-powered by commercially available 1.5 V AA batteries Valve thread connection M30x1.5 mm Nominal stroke 2.5 mm...
  • Page 2 The SSA911.01TH wireless radiator valve actuator is designed to work on radiator valves of different manufacturers in HVAC applications using M30x1.5 thread. It operates the valve to control the water flow and controls the room temperature. The valve actuator works only in combination with Siemens Smart Thermostat RDS110.R and optionally with wireless repeater RCR114.1.
  • Page 3 15 %. Error codes In case of an actuator malfunction or communication error with the Smart Thermostat, an error code is shown on the display of the SSA911.01TH. See Error codes [ Type summary Type Stock no.
  • Page 4 The theft protection kit secures the actuator; it prevents the batteries from being removed and the actuator from being unscrewed from the radiator valve without the use of a tool. Equipment combinations Siemens valves The SSA911.01TH is suited for use with the following types of Siemens radiator valves: Type Data sheet [m3/h] VDN1.., VEN1..
  • Page 5 Third-party valves without adapter The SSA911.01TH can operate third-party radiator valves without adapter, provided they have a M30x1.5 mm connecting thread and meet the following requirements: Force 90 N nominal Fully closed x > 9.0 mm Fully open 14.5 mm Valves of the following manufacturers may be used with the SSA911.01TH:...
  • Page 6 Do not mix new and used batteries. Store, transport and dispose of the batteries in compliance with local requirements, regulations and laws. Also observe the instructions of the battery manufacturer. Siemens A6V11739247_en--_b Phone : 2534 3066, 2534 5625, 2534 5587 Hindustan Hydraulics &...
  • Page 7 2. Remove plastic slip securing the batteries from the SSA911.01TH and wait for the actuator to start up (approximately 5 s) 3. Press the button on the SSA911.01TH for automatic calibration process (> 2 s) and wait for the confirmation of the calibration on the display 4.
  • Page 8 (> 2 s) confirms the chosen function yes: appears after confirming the function (except during factory reset) Go: indicates the confirmed function is starting Siemens A6V11739247_en--_b Phone : 2534 3066, 2534 5625, 2534 5587 Hindustan Hydraulics & Pneumatics, Chennai - 01.
  • Page 9 SSA911.01TH. Error codes cannot be acknowledged on the SSA911.01TH. The error code is shown on the display for as long as the error is active and will disappear once normal status has been reached.
  • Page 10 NOTICE Dismounting the Smart Valve Actuator Dismounting the SSA911.01TH while the stem is extended puts the actuator in an unde- fined state that makes re-mounting the actuator without damaging it very difficult. Before dismounting the SSA911.01TH from the valve, always perform either a new me- chanical adaptation to the radiator valve or a factory reset to retract the stem.
  • Page 11 Comply with all local and currently applicable laws and regulations. Dispose of empty batteries in designated collection points. Warranty Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations". Siemens rejects any and all warranties in the event that third-party products are used.
  • Page 12 For residential, commercial, and industrial environments EU conformity (CE) A5W00090263 EAC compliance Eurasian compliance for all SSA.. A6V11739247_en--_b Siemens Phone : 2534 3066, 2534 5625, 2534 5587 Hindustan Hydraulics & Pneumatics, Chennai - 01. 2021-09-03 Smart Infrastructure E-Mail : hhp@hindustanhydraulic.in...
  • Page 13 White NCS S 052-G Thread M30x1.5 W x H x D See Dimensions [ Weight Completely mounted Documents can be downloaded at http://www.siemens.com/bt/download Dimensions Dimensions in mm [kg] 0.305 Siemens A6V11739247_en--_b Phone : 2534 3066, 2534 5625, 2534 5587 Hindustan Hydraulics & Pneumatics, Chennai - 01.
  • Page 14 Revision numbers Type Valid from rev. no. SSA911.01TH ..01 S55181-A101 Issued by © Siemens Switzerland Ltd, 2020 Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies...