Summary of Contents for Siemens OpenAir GEB Series
Page 1
Damper actuators 15 Nm / 35 Nm (non-spring return) with Modbus communication ● GEB.. 15 Nm nominal torque ● GIB.. 35 Nm nominal torque ● Modbus RTU communication ● Operating voltage AC 24 V ● For air-handling units (AHU) and other ventilation applications A6V101037253_en--_a Siemens 2017-02-17 Building Technologies...
Page 3
Installation Instruction Installation of types with external Modbus interface A6V101006034 Related documents such as environmental declarations, CE declarations, etc., can be down- loaded at the following Internet address: http://siemens.com/bt/download Notes Safety Caution National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage.
Page 4
Comply with all local and currently applicable laws and regulations. Warranty Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations". Siemens rejects any and all warranties in the event that third-party products are used.
Mechanical fault, device jammed or manual override 1s on / 5s off Internal error 0.1s on / 1s off Invalid configuration, e.g. Min = Max Blue Flashes 1x after address display Bus termination is set active. 5 / 14 A6V101037253_en--_a Siemens 2017-02-17 Building Technologies...
Page 6
An address can be stored at any time, i.e. after setting the 1-digits, or after setting the 1- and the 10-digits. 5. Entered address is repeated one times for confirmation. Note: If button is released before LED shines red, the address is discarded. 6 / 14 Siemens A6V101037253_en--_a Building Technologies 2017-02-17...
Page 7
1. Enter addressing mode 2. Set 1-digits: Press button 5-times ⇓ LED flashes green per button press Store address: press button until LED shines red ⇓ address is stored and displayed 1x for confirmation 7 / 14 A6V101037253_en--_a Siemens 2017-02-17 Building Technologies...
Factory Index 1282-83 Factory Date Cf. product documentation Z4621 / Z4626 1284-85 Factory SeqNo 1409-16 TypeASN [Char_16..1] The documents can be downloaded from http://siemens.com/bt/download Register 769 “Status” Status Bit 00 1 = reserved Bit 06 1 = Adaption done Bit 01...
Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 / 115.2 Default: Auto Termination 120 Ω electronically switchable Default: Off Connection cables Cable length 0.9 m Power supply / Number of cores and cross-sectional area 5 x 0.75 mm Communication 9 / 14 A6V101037253_en--_a Siemens 2017-02-17 Building Technologies...
Page 10
GEB.. (round / square shaft) 6.4…20.5 mm / 6.4...13 mm GIB.. (round / square shaft) 8.0…25.6 mm / 6.0...18 mm Min. drive shaft length 20 mm The documents can be downloaded from http://siemens.com/bt/download 10 / 14 Siemens A6V101037253_en--_a Building Technologies 2017-02-17...
Page 11
The operating voltage at terminals G and G0 must comply with the requirements under SELV or PELV. Safety transformers with twofold insulation as per EN 61558 required; they must be designed to be on 100 % of the time. 11 / 14 A6V101037253_en--_a Siemens 2017-02-17 Building Technologies...
Page 12
24,8 P1...P3 1...9 S1...S6 Ø 8... 25,6 mm ν 6... 18 mm min. 100 Taptite M6 x 16 min. 60 15,5 4626M03 External Modbus Interface X = 220 mm Dimensions in mm 12 / 14 Siemens A6V101037253_en--_a Building Technologies 2017-02-17...
Page 13
13 / 14 A6V101037253_en--_a Siemens 2017-02-17 Building Technologies...