Accessories, spare
parts
Technical data
AC 24 V supply
(SELV/PELV)
AC 230 V supply
Function data
Positioning signal for GEB16..1
Characteristic functions
for GEB161.1, GEB166.1
for GEB163.1, GEB164.1
Position indicator
for GEB16...1
Feedback potentiometer
for GEB132.1 / GEB332.1
Auxiliary switches
for GEB..6.1 / GEB164.1
Connection cables
Degree of protection of housing
Protection class
Environmental conditions
Standards and directives
Dimensions
Weight
Siemens
Building Technologies
Accessories to functionally extend the actuators are available, e.g., rotary/linear sets,
auxiliary switches (1 or 2 switches) and weather protection cover; see data sheet
N4697.
Operating voltage / Frequency
Power consumption GEB13..1: Running
GEB16..1: Running
Operating voltage / Frequency
Power consumption GEB33..1
Nominal torque
Maximum torque (blocked)
Nominal rotary angle / Max. rotary angle
Runtime for 90° rotary angle
Input voltage Y (wires 8-2)
Max. permissible input voltage
Input voltage Y (wires 8-2)
Non-adjustable characteristic function
Adjustable characteristic function
Output voltage U (cores 9-2)
Max. output current
Change of resistance (wires P1-P2)
Load
Contact rating
Voltage (no mixed operation AC 24 V / AC 230 V)
Switching range for auxiliary switches
Setting increments
Cross-section
Standard length
Degree of protection as per EN 60 529 (note mounting instructions) IP 54
Insulation class
AC 24 V, feedback potentiometer
AC 230 V, auxiliary switch
Operation / Transport
Temperature
Humidity (non-condensing)
Product safety: Automatic electrical controls for household and
similar use
Electromagnetic compatibility
(Application)
EU Conformity (CE)
RCM Conformity
Product environmental declaration
Actuator W x H x D (see "Dimensions")
Damper shaft:
Round
Square
Min. shaft length
Without packaging: GEB1...1
GEB33..1
1)
The documents can be downloaded from
2)
The product environmental declaration contains data on environmentally compatible product design
and assessments (RoHS compliance, materials composition, packaging, environmental benefit,
disposal).
Air damper actuators GEB...1, rotary version
Holding
Offset Uo
Span U
2)
http://siemens.com/bt/download
AC 24 V
20 % / 50/60 Hz
4 VA / 3.5 W
6 VA / 5.5 W
1.5 W
AC 230 V
10 % / 50/60 Hz
3 VA / 3 W
15 Nm
30 Nm
90° / max. 95°
2°
150 s (50 Hz) / 125 s (60 Hz)
DC 0...10 V / DC 2...10 V
DC 35 V
DC 0...35 V
DC 0...10 V / DC 2...10 V
DC 0...5 V
DC 2...30 V
DC 0...10 V
DC
1 mA
0...1000
< 1 W
6 A resistive, 2 A inductive
AC 24...230 V
5°...90°
5°
2
0.75 mm
0.9 m
EN 60 730
lll
ll
IEC 721-3-3 / IEC 721-3-2
32...+55 °C / 32...+70 °C
< 95% r. h. / < 95% r. h.
EN 60 730-2-14
(Type 1)
For residential, commercial and
industrial environments
1)
A5W00004376
1)
A5W00004377
1)
CE1E4621en
81 x 192 x 63 mm
6.4...20.5 mm
6.4...13 mm
20 mm
1 kg
1.1 kg
CM2N4621en
2016-01-29
3/6