Disposal
Internal diagrams
Cable labeling
4/6
Siemens
Building Technologies
The device is considered an electronics device for disposal in terms of
European Directive 2012/19/EU and may not be disposed of as domestic
garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and
regulations.
GEB13..1 / GEB33..1
Three-position control
AC 0 V
0...1000
6
7
P1 P2
P3
GEB13...
100%
M
0%
1
AC 24 V
0...1000
AC 230 V
6
7
P1 P2
P3
GEB33...
100%
M
0%
4
Pin
Code
No.
Actuators AC 24V
G
1
G0
2
Y1
6
Y2
7
Y
8
U
9
Actuators AC 230V
N
4
Y1
6
Y2
7
Auxiliary switch
Q11
S1
Q12
S2
Q14
S3
Q21
S4
Q22
S5
Q24
S6
Positioner
a
P1
b
P2
c
P3
Air damper actuators GEB...1, rotary version
AC 24 V...230 V / 6 (2) A
S1
S4
A
B
GEB16...
S2 S3
S5 S6
AC 24 V...230 V / 6 (2) A
S1
S4
A
B
S2 S3
S5 S6
Cable
Color
Abbreviation
red
RD
black
BK
purple
VT
orange
OG
gray
GY
pink
PK
blue
BU
black
BK
white
WH
gray/red
GY RD
gray/blue
GY BU
gray/pink
GY PK
black/red
BK RD
black/blue
BK BU
black/pink
BK PK
white/red
WH RD
white/blue
WH BU
white/pink
WH PK
GEB16..1
Modulating control
DC 0...10 V / 2...10 V / 0...35 V
AC 24 V
DC 0...10 V
AC 24 V...230 V / 6 (2) A
1
8
S1
100%
A
M
0%
S2 S3
2
9
DC 0...10 V
Meaning
System potential AC 24 V
System neutral
Control signal AC 0 V, clockwise
Control signal AC 0 V, counter-clockwise
Pos. signal DC 0...10 V, 2...10 V, 0...35 V
Position indication DC 0...10 V
Neutral conductor
Control signal AC 230 V, clockwise
Control signal AC 230 V, counter-clockwise
Switch A Input
Switch A Normally closed contact
Switch A Normally open contact
Switch B Input
Switch B Normally closed contact
Switch B Normally open contact
Potentiometer 0...100 % (P1-P2)
Potentiometer pick-off
Potentiometer 100...0 % (P3-P2)
S4
B
S5 S6
CM2N4621en
2016-01-29