Point Lists
2.2 Control Relay Output Blocks/Binary Output Status
2.2
Control Relay Output Blocks/Binary Output Status
Binary Output Status Points
Object Number: 10
Request Function Codes supported: 1 (Read)
Default Variation reported when variation 0 requested: 2 (Binary Output Status)
Control Relay Output Blocks/Binary Output Status
Object Number: 12
Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no
ack)
Point
Index
External Commands (double point commands)
0
52Breaker
1
52Breaker
2
Disc.Swit.
3
Disc.Swit.
4
GndSwit.
5
GndSwit.
Internal Commands
6
P-GrpA act
7
P-GrpB act
8
P-GrpC act
9
P-GrpD act
10
ModeREMOTE
1
The on-time is fixed within the SIPROTEC 4 parameter package for each command object.
The Control Relay Output Block information on-time will be ignored.
Changing the Setting Group
Switching on one setting group automatically switches off the current active setting group. Transmission of the
value OFF is insignificant for the change of the setting group and is refused by the device.
A change of the setting group is only possible via DNP3 if the parameter Change to Another Setting Group
(parameter address = 302) has the value "Protocol".
Control Mode REMOTE
Control mode with control authority is REMOTE, option of unlocked control with DNP3.
•
Changing the "Control mode REMOTE" to UNLOCKED permits one unlocked control operation via DNP3.
After execution of the command, the "Control mode REMOTE" in the SIPROTEC 4 device will automati-
cally be reset to LOCKED.
•
A programmed test "Switch in position" for unlocked control operations will always be executed.
If, after changing the "Control mode REMOTE" to UNLOCKED, no command is received via DNP3 for a period
of 5 minutes, then the "Control mode REMOTE" is automatically reset to LOCKED.
24
Name
Trip command for Circuit Breaker
Close command for Circuit Breaker
Trip command for Disconnect Switch
Close command for Disconnect Switch
Trip command for Ground Switch
Close command for Ground Switch
Select Setting Group A and deactivate Groups B, C, D Latch On
Select Setting Group B and deactivate Groups A, C, D Latch On
Select Setting Group C and deactivate Groups A, B, D Latch On
Select Setting Group D and deactivate Groups A, B, C Latch On
Mode REMOTE control; Latch On = UNLOCKED
Latch Off = LOCKED
SIPROTEC Compact, Feeder Protection and Recloser Controller 7SC80, Bus Mapping/Point Lists
Description
C53000-L2040-C353-3, Edition 09.2018
Supported Control
Relay Output Block Fields
Trip, Pulse On
1
(On Time Fixed
)
Close, Pulse On
1
(On Time Fixed
)
Trip, Pulse On
1
(On Time Fixed
)
Close, Pulse On
1
(On Time Fixed
)
Trip, Pulse On
1
(On Time Fixed
)
Close, Pulse On
1
(On Time Fixed
)
Latch On; Latch Off