n POWER REQUIREMENTS AND INPUT SPECIFICATIONS
Item
Power Supply
Max. Momentary Power Failure
In-Rush Current
Fuse
AL2-10MR-A, 240VAC~
AL2-10MR-A, 120VAC~
AL2-10MR-D, 24VDC
AL2-14MR-A, 240VAC~
Typical Power
AL2-14MR-A, 120VAC~
Consumption
AL2-14MR-D, 24VDC
AL2-24MR-A, 240VAC~
AL2-24MR-A, 120VAC~
AL2-24MR-D, 24VDC
n INPUT SPECIFICATIONS
Description
Input Voltage
Input Current
I01 – I06
AL2-10MR-_
I01 – I08
Input Current
AL2-14MR-
AL2-24MR-_
I09 – I15
Input Impedance
g
Off
On /
I01 – I15
g
On
Off
Response Time
Isolation Circuit
n ANALOG INPUT SPECIFICATIONS
(AL2-**MR-D, SOURCE TYPE ONLY)
Description
Analog Input Specification
AL2-10MR-D: 6 (I01 - I06)
Number of Analog Input
AL2-14MR-D, AL2-24MR-D: 8 (I01 - I08)
Input Voltage
0 - 10V DC
Analog Input Range
0 - 500 (10000/500 mV)
Conversion Speed
8ms
Input Impedance
142kΩ ± 5%
Overall Accuracy
± 5%, 0.5VDC
Temperature Drift
± 3 LSB
6
Mitsubishi Electric Automation, Inc.
Description
AL2-_ _MR-A: 100 - 240 VAC~,
+10% -15%, 50/60 Hz
AL2-_ _MR-D: 24VDC, +20% -15%
AL2-_ _MR-A: 10ms
AL2-_ _MR-D: 5ms
AL2-_ _MR-A: ≤ 6.5A (3.5A),
240VAC~ (120VAC~)
AL2-_ _MR-D: ≤ 7.0A, 24VDC
Rating
AL2-_ _MR-A: 250V 1A
AL2-24MR-D: 250V 500mA
AL2-14MR-D: 250V 500mA
AL2-10MR-D: 250V 1A
I/O all On - 3.5 W; I/O all Off - 1.85 W
I/O all On - 3.0 W; I/O all Off - 1.55 W
I/O all On - 2.5 W; I/O all Off - 0.75 W
I/O all On - 4.5 W; I/O all Off - 2.0 W
I/O all On - 3.5 W; I/O all Off - 1.5 W
I/O all On - 4.0 W; I/O all Off - 1.0 W
I/O all On - 5.5 W; I/O all Off - 2.5 W
I/O all On - 4.5 W; I/O all Off - 2.0 W
I/O all On - 5.0 W; I/O all Off - 1.0 W
AL2-_ _MR-D (DC Inputs)
AL2-_ _MR-A
(AC Inputs)
Source Type
Sink Type
100 - 240V
AC~, +10
24V DC, +20% -15%
-15%, 50/60 Hz
0.13mA, 120
VAC~
6.0mA,
0.25mA, 240
24VDC
VAC~
5.5mA,
24VDC
0.15mA, 120V
AC~
5.5mA,
0.29mA, 240
24VDC
VAC~
≥ 800kΩ
-
≥ 80V / ≤ 40V
≥ 18V / ≤ 4V
≤ 4V / ≥18V
35-85ms, 120
VAC~
10 - 20ms
25-130ms,
240VAC~
None
None
n GENERAL SPECIFICATIONS
Description
Specifications
(-25) - 55°C / (-13) - 131°F,
Operating Temperature
Displayed: (-10) - 55°C / 14 - 131°F
Storage Temperature
(-30) - 70°C / (-22) - 158°F
Humidity
35 - 85% relative humidity, no condensation
Device and RTC Backup
20 days (25°C / 77°F) by capacitor
RTC Accuracy
5 s / day (25°C / 77°F)
Noise Immunity
1000 Vpp, 1 μs, 30 - 100Hz, tested by noise simulator
3750V AC~ > 1 min per EN60730-1 between the
following points:
Dialectric Withstand
Power/Input Terminals and Relay Output Terminals
Voltage
Relay Output Terminal and Relay Output Terminal
All Terminals and the DIN 43880 Control box or
equivalent
7 MΩ, 500VDC per EN60730-1 between the following
points: Power/Input Terminals and Relay Output
Insulation Resistance
Terminals; Relay Output Terminal and Relay Output
Terminal; All Terminals and the DIN 43880 Control box
or equivalent
Conforms to IEC 68-2-6; 10-57 Hz: 0.15 mm
Vibration Resistance -
Constant Amplitude 57-150 Hz: 19.6 m/s²
Direct Mounting
Acceleration Sweep Count for X, Y, Z: 10 times
(80 minutes in each direction)
Conforms to IEC 68-2-6; 10-57 Hz: 0.075 mm
Vibration Resistance -
Constant Amplitude 57-150 Hz: 9.8 m/s²
DIN Rail Mounting
Acceleration Sweep Count for X, Y, Z: 10 times
(80 minutes in each direction)
Conforms to IEC 68-2-27: 147m/s² Acceleration,
Shock Resistance
Action Time: 11 ms 3 times in each direction X, Y, Z
Type of Action
EN60730-1, Section 6.4.3 - Type 1C (Relay Output)
Software Class
EN60730-1, Section H6.18 - Class A
Purpose of Control
EN60730-1, Section 2.2 - Electrical Control
Construction of Control
EN60730-1, Section 6.15 - Incorporated Control
Whether the Control is
EN60730-1, Section H2.5.7 - Electronic Control
Electric
Safety Class
II
Protection
IP20
Temperature for the Ball
75°C (167°F)
Pressure Test
Pollution Degree
2
Operation Ambiance
To be free of corrosive gases. Dust should be minimal
Electrical Isolation
Reinforced primary / secondary insulation
Grounding
None
EC Directive: EMC
EN61131-2:2007; EN60730-1:2011
EC Directive: LVD
EN61131-2:2007; EN60730-1:2011
Certification of UL/cUL
File number: E95239
n OUTPUT SPECIFICATIONS
Description
Switched Voltage
AL2-10MR-_ (O01 - O04)
Max.
AL2-14MR-_ (O01 - O06)
Resistive
AL2-24MR-_ (O01 - O04)
Load
AL2-24MR-_ (O05 - O09) 2A/point (4A/COM)
AL2-10MR-_ (O01 - O04)
Contact
AL2-14MR-_ (O01 - O06)
Life Cycle /
AL2-24MR-_ (O01 - O04)
Resistance
Load
AL2-24MR-_ (O05 - O09)
Minimum Load
AL2-10MR-_ (O01 - O04)
AL2-14MR-_ (O01 - O06)
Max.
Inductive
AL2-24MR-_ (O01 - O04)
Load
AL2-24MR-_ (O05 - O09)
Response Time
Operation Indication
Isolation Circuit
Relay Specification
250VAC~ or less, 30VDC or less
8A/COM
100,000 Cycles at 8 Amps /
240VAC~ or 24VDC
100,000 Cycles at 2 Amps / 240VAC~
or 24VDC
50mW (10mA at 5VDC)
249 VA (1/3 hp) / 125VAC~,
373 VA (1/2 hp) / 250VAC~
93 VA (1/8 hp) / 125VAC~,
93 VA (1/8 hp) / 250VAC~
≤ 10 ms
Liquid Crystal Display
By Relay