hit counter script

Installing On The S7-1500 Standard Rail - Siemens SCALANCE S615 Operating Instructions Manual

Simatic net industrial ethernet security
Hide thumbs Also See for SCALANCE S615:
Table of Contents

Advertisement

Installation and removal

4.6 Installing on the S7-1500 standard rail

4.6
Installing on the S7-1500 standard rail
Installation
1. Place the first housing guide of the device on the top edge of the standard rail ①.
2. Using a screwdriver, pull down the catch ② on the rear of the device.
3. Swing the device down while pulling down the catch ③. After it is released, the spring catch
locks in place.
4. Connect the power supply, refer to the section "Power supply (Page 51)".
5. Fit the connectors for the digital input and digital output, refer to the section "Digital
input/output (Page 53)".
6. Connect the device to the local network, refer to the section "Ethernet port (Page 55)".
7. Connect the terminal with as short a cable as possible ≤ 150 mm and a large cross-sectional
area of 1.5 mm² to the functional ground of the system, see section "Terminals (Page 25)"
and section "Grounding (Page 52)".
Dismantling
1. Disconnect all connected cables.
2. Using a screwdriver, pull down the catch on the rear of the device.
3. Remove the device from the standard rail.
40
Operating Instructions, 10/2022, C79000-G8976-C389-07
SCALANCE S615

Advertisement

Table of Contents
loading

This manual is also suitable for:

Scalance s615 eec6gk5 615-0aa00-2aa26gk5 615-0aa01-2aa2Simatic net scalance s615Simatic net scalance s615 eec

Table of Contents