hit counter script

Programming; Creating Technology Data Blocks - Siemens SIMATIC 317TF-2 DP Getting Started

Automation system s7-300
Table of Contents

Advertisement

Programming

5.1

Creating technology data blocks

Use "Technology Objects Management" to generate a technology DB for each TO. Do not
copy the technology DBs in order to ensure a defined assignment between the technology
DB and its TO.
Procedure
Step
Activity
1
Change to "Technology Objects Management". Confirm the first message box with "OK", and the second
with "Yes".
If you are not running the "Technological Objects Management" application yet, you can open it by double-
clicking "Technological Objects" in the "Technology" folder in SIMATIC Manager (see also step:
"Configuring the axes with S7T Config").
Result: The "Technological Objects Management" opens.
Edit the DB numbers as shown in the figure in order to adapt these for use in our example.
2
Create the technology DBs listed below by clicking "Create":
Axis_1
Axis_2 (if this exists)
Trace
MCDevice
CPU 317TF-2 DP: Controlling a SINAMICS S120 with Safety Functions
Getting Started, 07/2010, A5E02982990-01
Result
The system generates the technology data
blocks DB1, DB2, DB3 or DB4.
5