7.7
Security (6.)
7.7.1
Remote access (6.1.)
7.7.1.1
Remote lockout (6.1.1.)
Description
Options
Factory setting
Note
If access control is changed to limit remote access, it can be reset only via the handheld
programmer.
7.7.2
Local access (6.2.)
7.7.2.1
Write protection (6.2.1.)
Description
Handheld
programmer
values
Note
Do not lose this number value.
7.7.2.2
Local operation (6.2.2.)
Description
Options
Factory setting
In SIMATIC PDM, open the menu Device – Write Locking, select On or Off, and click on
Transfer.
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF
Enables or disables programming via the network and PDM.
OFF (remote operation enabled)
ON (remote operation disabled
OFF
Prevents any changes to parameters via PDM or the hand-held programmer.
Range: 0 to 99999
2457 (unlock value)
any other value
Enables or disables programming via the hand-held programmer.
ENABLED
DISABLED
ENABLED
Parameter assignment
Off (enables programming)
On (disables programming)
7.7 Security (6.)
137