Parameters/address space
4.2 Parameters
The following parameter settings are possible:
Table 4- 2
Configurable parameters and their defaults (GSD file)
Parameter
Diagnostics:
No supply voltage L+
Diagnostics:
Short-circuit to ground
Diagnostics:
Overflow
Diagnostics:
Underflow
Diagnostics:
Wire break
Type/range of meas-
urement
Smoothing
14
Range of values
Disable
•
Enable
•
Disable
•
Enable
•
Disable
•
Enable
•
Disable
•
Enable
•
Disable
•
Enable
•
Deactivated
•
Current (4-wire connec-
•
tion) 0 to 20 mA
Current (4-wire connec-
•
tion) 4 to 20 mA
Current (4-wire connec-
•
tion) +/-20 mA
Current (2-wire connec-
•
tion) 0 to 20 mA
Current (2-wire connec-
•
tion) 4 to 20 mA
None
•
Weak
•
Medium
•
Strong
•
Default
Reconfigura-
tion in RUN
Disable
Yes
Disable
Yes
Disable
Yes
Disable
Yes
Disable
Yes
Current (4-wire
Yes
connection)
4 to 20 mA
None
Yes
Analog input module AI 8xI 2-/4-wire BA (6ES7134-6GF00-0AA1)
Effective range with configura-
tion software, e.g. STEP 7
(TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS
DP
Module
Module
Module
Module
Module
Module
Module
Module
Module
Channel
Channel
Channel
Channel
Manual, 03/2015, A5E34941201-AA
1