2.1 Inventory
The 5895XL ships with the following hardware:
•
A cabinet with all hardware assembled
•
Two keys for the front door
•
Ten 4.7K ohm end-of-line resistors
NOTE: For UL installations, 4.7kΩ end-of-line resistor (ordered separately) must be used.
•
A battery cable for batteries wired in series
2.2 Environmental Specifications
It is important to protect the 5895XL control panel from water. To prevent water damage, the following conditions should be observed when
installing the units:
•
Do not mount directly on exterior walls, especially masonry walls (condensation).
•
Do not mount directly on exterior walls below grade (condensation).
•
Protect from plumbing leaks.
•
Protect from splash caused by sprinkler system inspection ports.
•
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery).
When selecting a location to mount the 5895XL, the unit should be mounted where it will NOT be exposed to temperatures outside the range
of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) non-condensing.
2.3 5895XL Board and Terminal Strip Description
Figure 2.1 shows the 5895XL circuit board including location of terminals, the DIP switch for setting module ID, and the LED.
10
Section 2: Before You Begin Installing
AC Power
N
G
L
3
2
1
LED
DIP switches
for setting ID
33
32
31
30
29
28
27
26
25
24
-
+
A
B
N.O.
C
N.C.
N.O.
C
N.C.
MAIN SBUS IN OUT
/
RELAY 1
RELAY 2
for connection
conventional
to FACP or to
relay circuits
controlling
5895XL if daisy-
chained
Figure 2.1 5895XL Board Layout
23
22
21
20
19
18
17
16
15
14
13
-
+
A
B
-
+
A
B
O
X
O
SBUS IN
SBUS OUT
I/O 1
I/O 2
SBUS module
regulated Flexput circuits
connections
5895XL Manual — P/N 151142-L8:M 2/15/2022