CC-Link IE TSN structure
Window
In this manual, "Authentication Class" is described as "CC-Link IE TSN Class".
Displayed items
Item
RX Setting, RY
Points
Setting
Start
End
RWr Setting, RWw
Points
Setting
Start
End
IP Address
Network Synchronous
Communication Setting
Communication Period Setting
CC-Link IE TSN Class
If the CC-Link IE TSN Class set by function setting switch 2 and the CC-Link IE TSN Class set in the network
configuration settings are set to different values, event code 00C81H will be recorded in the event history of
the master station and the FPGA module will not establish a data link.
9 PARAMETER SETTING
134
9.2 For CC-Link IE TSN Communication Mode
Description
Set the assignment of RX/RY points.
The RX/RY start number is displayed.
The RX/RY end number is displayed.
Set the assignment of RWr/RWw points.
The RWr/RWw start number is displayed.
The RWr/RWw end number is displayed.
Set the IP address of the FPGA module to be connected.
If the set IP address is different from the IP address set with the IP address/station
number setting switch, cyclic transmission with the master station cannot be
performed and data link will not be established. ( Page 54 IP address/station
number setting switch setting)
Sets whether to use the CC-Link IE TSN Network synchronous communication
function.
Sets the cycle of the FPGA module when setting multiple communication cycles. If
the master station and FPGA module have different communication speeds, there
are restrictions on the setting range. ( Page 132 Communication cycle interval
setting)
Sets the CC-Link IE TSN Class of the FPGA module. Make the same settings as
the CC-Link IE TSN Class set on the FPGA module. ( Page 58 Setting the
function setting switches)
Setting range
0 to 112 (Default value: 112)
0 to 144 (Default value: 144)
0.0.01 to 223.255.255.254
• Do not Synchronize (Default)
• Synchronize
• Basic Period
• Normal-Speed
• Low-Speed
• CC-Link IE TSN Class B
• CC-Link IE TSN Class A