Error code
Classification
(hexadecimal)
*1*2
D028H
Minor
*1 This error occurs only once when an abnormality is detected. Before clearing the error, eliminate the cause of the error and check that a
data link is established.
*2 When this error occurs, errors other than this error may not occur. If this error occurs, eliminate the cause of one error after another until
a data link is established.
24 ERROR CODE LIST
462
Error name
Description and cause
Communication
The communication cycle that cannot be
cycle setting error
handled by the FPGA module is set while
(CC-Link IE TSN
the FPGA module is operating with CC-
Class A)
Link IE TSN Class A.
Action
Correct the communication cycle setting so
that the FPGA module can operate with the
set communication cycle.