hit counter script

Mitsubishi Electric NZ2GN2S-D41P01 User Manual page 497

Cc-link ie tsn fpga module
Table of Contents

Advertisement

Function setting switch state monitor
■Address
Name
Function setting switch state monitor
■Description
The ON/OFF status of function setting switches 1 to 10 can be checked.
At what point ON, OFF status is displayed differs depending on the function setting switch.
• Function setting switch 1 and function setting switch 3: ON/OFF status when the module power supply is ON
• Function setting switch 4 to function setting switch 10: Current ON/OFF state
b15
b14
b13
b12
0 (fixed)
(1) Function setting switch 1
(2) Function setting switch 2
(3) Function setting switch 3
(4) Function setting switch 4
(5) Function setting switch 5
(6) Function setting switch 6
(7) Function setting switch 7
(8) Function setting switch 8
(9) Function setting switch 9
(10) Function setting switch 10
• 0: OFF
• 1: ON
Firmware version
■Address
Name
Firmware version
■Description
The firmware version of the FPGA module can be checked.
FPGA version
■Address
Name
FPGA version
■Description
The version of the FPGA module can be checked.
b11
b10
b9
b8
(10)
(9)
Remote buffer memory address
0902H
b7
b6
b5
b4
(8)
(7)
(6)
(5)
Remote buffer memory address
0903H
Remote buffer memory address
0904H
Appendix 3 Remote Buffer Memory
b3
b2
b1
b0
(4)
(3)
(2)
(1)
APPX