Page 1
MULTI MULTI OUTDOOR UNIT INSTALLATION MANUAL Multi-Zone Heat Pump Systems 1.5 to 5 Tons Dual and Tri-Zone Quad-Zone Eight-Zone Multi F Multi F Multi F MAX...
Page 17
Branch distribution Unit can accommodate from one (1) indoor unit up to four (4) indoor units depending on the ports available on the branch distribution Unit. Communication / power (connection) cable must be a minimum of 14 AWG, 4-conductor from the outdoor unit to the branch distribution unit (Multi F MAX systems only), and 14 AWG, 4-conductor from the branch distribution unit to the indoor unit, stranded, shielded or unshielded (if shielded, it must be grounded to the chassis of the outdoor unit only), and must comply with applicable local and national codes.
• A location that allows for optimum air flow and is easily accessible for inspection, maintenance, and service. • Where piping between the outdoor unit and indoor unit (and branch distribution unit[s], if Multi F MAX) is within allowable limits.
Page 25
• Maintains coil heat transfer efficiency by reducing the number of and shortening the cycle time for defrost operation. • Easier maintenance and servicing during inclement weather. • When mounted in a fully enclosed space, limiting the ambient air temperature will allow the Multi F / Multi F MAX system designer to elimi- nate oversizing.
Page 28
Select a location for installing the indoor units that will meet the following conditions: • Within allowable parameters for proper connection to the outdoor unit (and branch distribution unit, if a Multi F MAX system). • So that condensation drainage can be conveniently routed away.
Bolt Branch Distribution Unit Orientation Multi F MAX branch distribution (BD) units can be installed in a multitude of options to fit various building This material is for informational configurations and job or application requirements (suspended from the ceiling or mounted on the wall).
LG offers, free of charge, LG Air Conditioner Technical Solution (LATS) software—a total design solution for LG air conditioning systems. To reduce the risk of designing an improper applied system or one that will not operate correctly, LG prefers that LATS software be used on all projects.
Page 34
LATS can generate an Excel GERP report that can imported into the LG SOPS pricing and ordering system.
Page 35
LMU600HV = 8 One of the most critical elements of Multi F and Multi F MAX systems is the refrigerant piping. See below and the following pages for pipe length limits that must be followed in the design of Multi F and Multi F MAX refrigerant pipe systems.
Always follow local codes when selecting and installing copper pipe and piping system components. Approved piping for use with LG HVAC products will be marked “R410 RATED” along the length of the pipe. Piping wall thickness must meet local code requirements and be approved for a maximum operating pressure of 551 psi. When bending piping, try to keep the number of bends to a minimum, and use the largest radii possible to reduce the equivalent length of installed piping;...
Failure to do so will cause significant performance degradation. Proper leak checks must be performed. Using isolation valves does not automatically void any LG product warranty, however, a limited warranty will be voided in whole or part must any field supplied accessory fail in any way that causes product failure.
Page 45
Pipe Sleeves at Penetrations LG recommends that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and promote free movement of the pipe within the sleeve.
MULTI Flaring and Brazing Procedures One of the main causes of refrigerant leaks is a defective connection. For LG HVAC systems, the installer needs to know how perform both flared and brazed connections successfully. • During installation, it is imperative to keep the piping system free of contaminants and debris such as copper burrs, slag, or carbon dust.
Page 50
INSTALLING MULTI F MAX SYSTEMS MULTI For Multi F MAX outdoor units, piping can be installed in one of four directions: front, side, back, and down (A). If the downward installation is chosen, the knockout hole in the base pan must be accessed (B).
Page 62
• ARE ground terminals. • • Always create a wiring diagram that contains the exact sequence in which all the indoor units and branch distribution units (Multi F MAX systems only) are wired in relation to the outdoor unit. •...
Page 64
(1[L1]) and Neutral (2[L2]) Cable at Least Two (2) Inches for Each Indoor Unit Outdoor and Indoor Unit appearances may vary depending on the model. Figure 81: Schematic of a Multi F MAX System When the Wiring is GREATER THAN 130 Feet. At Least Two (2) Inches...
Page 73
Figure 92: PI-485 Board (Ap- pearance will differ depending on PI-485 V-net Control Integration Board for Outdoor Units adapt Multi F / Multi F MAX systems to a LG model). VRF system central protocol for integration with LG central controllers. The PI-485 is installed in the Multi F / Multi F MAX outdoor unit.
Page 74
ELECTRICAL From Indoor Units to Remote Controllers • Communication cable from indoor unit to remote controller(s) is to be LG supplied or field supplied 22 AWG, 3-conductor, twisted, stranded, unshielded. Wiring must comply with all applicable local and national codes.
After the refrigerant piping installation is complete, perform a triple leak / pressure test. Triple leak / pressure test is performed between the outdoor unit and indoor units (and branch distribution units [Multi F MAX only]) to verify that refrigerant can flow through the system without danger of leaks or pressure losses.
Page 77
Schrader ports on the outdoor unit service ports. The triple evacuation procedure seen on page 78 is a best practices recommendation for Multi F systems, but mandatory for Multi F MAX systems. For faster evacuation, the Schrader core can be removed, and an auxiliary service port can used. Make sure to re-install the original Schrader core before operating the system.
Page 78
MAX systems. The deep evacuation procedure is insufficient to fully evacuate the extensive piping systems on Multi F MAX products. Triple evacuation must be performed through the Schrader ports on the outdoor unit service ports. The triple evacuation procedure is a best practices recommendation for Multi F systems, but mandatory for Multi F MAX systems.
Page 80
FINAL INSTALLATION PROCEDURES MULTI LG Multi F and Multi F MAX outdoor units ship from the factory with a charge of Table 34: Outdoor Unit Factory Charge. R410A refrigerant. A trim charge will need to be added to take into account addition-...
1. Operate the system in cooling mode for 15 to 20 minutes. 2. Evaluate performance as the system runs, verifying the outdoor unit, and all indoor units and branch distribution units (Multi F MAX sys- tems only) are working properly. Make notes as needed to address any issues that might be found.
Page 98
All literature and bagged accessories have been removed from the fan discharge (ducted and cassette model indoor units). All indoor units and branch distribution unit(s) (Multi F MAX only) are installed, properly supported, and located indoors in a non-corrosive environment.
Page 99
The power supplied was clean with voltage fluctuations within specifications (±10% of nameplate). Power wiring to the Multi F / Multi F MAX outdoor unit was field supplied, solid or stranded, and installed per all local, state, and NEC requirements.
Page 104
20001747 ISO 9001: 2008 LG ELECTRONICS INC. LG Electronics, U.S.A., Inc. IM_MultiF_ODU_04_20 Air Conditioning Technologies Supersedes: IM_MultiF_ODU_03_17 4300 North Point Parkway IM_MultiF_ODU_11_16 Alpharetta, Georgia 30022 IM_MultiF_ODU_4_16 www.lghvac.com IM_MultiF_ODU_11_15...
Page 105
MULTI MULTI OUTDOOR UNIT INSTALLATION MANUAL Multi-Zone Heat Pump Systems 1.5 to 5 Tons Dual and Tri-Zone Quad-Zone Eight-Zone Multi F Multi F Multi F MAX...
Page 113
(WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). the BD unit (Multi F MAX systems only), and 18 AWG from the BD unit to the indoor unit, Rated heating capacity obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF stranded, shielded or unshielded (if shielded, it must be grounded to the chassis of the wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Page 114
Branch Distribution Unit can accommodate from one (1) indoor unit up to four (4) indoor units depending on the ports available on the Branch Distribution Unit. All power wiring / communication cable to be minimum 16 AWG from the outdoor unit to the BD unit (Multi F MAX systems only), and 18 AWG from the BD unit to the indoor unit, stranded, shielded or unshielded (if shielded, it must be grounded to the chassis of the outdoor unit only), and must comply with applicable local and national codes.
• A location that allows for optimum air flow and is easily accessible for inspection, maintenance, and service. • Where piping between the outdoor unit, indoor unit(s), and BD units (Multi F MAX systems only) are within allowable limits. • Include space for drainage to ensure condensate flows properly out of the unit when it is in heating mode. Avoid placing the outdoor unit in a low-lying area where water could accumulate.
Page 124
Selecting the Best Location for the Branch Distribution (BD) Unit Branch Distribution (BD) units are used only with Multi F MAX systems to distribute the refrigerant from the outdoor unit to up to eight indoor units. Select location indoors that will meet the following conditions: •...
Page 129
Align the center of the piping, and initially hand tighten the flare nuts using three (3) or four (4) turns. For Multi F Outdoor Units, install the flare nuts by: 1.
Contaminants can result in mechanical failure of the system. All joints are brazed in the field. Multi F / Multi F MAX refrigeration system components contain very small capillary tubes, small orifices, electronic expansion valves, oil separators, and heat exchangers that can easily become blocked. Proper system operation depends on the installer using best practices and utmost care while assembling the piping system.
Page 131
Selecting Field-Supplied Copper Tubing Type ACR copper is the only approved refrigerant pipe material for use with LG Multi F air conditioning products. ACR rated tubing is the only type that ships with yellow caps. Approved tubing for use with Multi F products will be marked “R410 RATED” along the length of the tube.
Page 133
No Pipe Size Substitutions Use only the pipe size selected by the LATS Multi F pipe system design software or as conveyed in the product installation instructions. Using a different size is prohibited and may result in a system malfunction or failure to work at all.
Page 136
Components such as oil traps, solenoid valves, filter-dryers, sight glasses, tee fittings, and other after-market accessories are not permitted on the refrigerant piping system between the outdoor units and the indoor / branch distribution units. Multi F and Multi F MAX systems are provided with redundant systems that assure oil is properly returned to the compressor.
Piping Length and Elevation Limitations One of the most critical elements of Multi F and Multi F MAX systems is the refrigerant piping. The tables on the next few pages list pipe length limits that must be followed in the design of Multi F and Multi F MAX refrigerant pipe systems.
Leak Test and Vacuum Procedures Before performing the test run, Multi F and Multi F MAX refrigerant piping and the piping connections to the outdoor unit, the indoor units, and the BD units (Multi F MAX systems only) must be evacuated to remove any non-condensible gases and moisture that may be present in the system, and checked for leaks.
MULTI Refrigerant Charge LG Multi F and Multi F MAX outdoor units ship from the factory with a charge of Table 34: Outdoor Unit Factory Charge. R410A refrigerant. A trim charge may need to be added to take into account...
Refrigerant Piping System Insulation All refrigerant piping from the outdoor unit to the indoor units / BD units (Multi F MAX systems only) must be insulated correctly for safety and usage. Y-branch connections, refrigerant piping, field-provided isolation ball valves (if present), service valves, and elbows must be properly and completely insulated using closed cell pipe insulation (up to the indoor unit piping connections).
Page 158
General Information General Communication Cable Specifications • Multi F Systems: All power wiring / communication cable to be minimum 18 AWG from the Figure 72: Multi F / Multi F MAX Outdoor and Indoor / Branch Distribution Unit Wiring and outdoor unit to the indoor unit, stranded, shielded or unshielded (if shielded, it must be Communications Cable Diagram.
3. Draw the power wiring to the outdoor unit, and the power wiring / communications cable (connecting cable) to the indoor units or BD unit (Multi F MAX systems only), through field-supplied conduits. Ensure there is enough length to connect the wiring / cables to the terminals on the outdoor unit.
Page 162
3. Provide strain relief by securing the wiring / cable to the indoor unit with the factory-supplied clamps. 4. For more installation information for specific indoor units, refer to the separate indoor unit installation manuals on www.lg-dfs.com. Distributor (BD) Unit (Multi F MAX Systems Only)
Page 163
PI485 ance may differ depending on PI485 V-net Control Integration Board for Outdoor Units adapt Multi F, Multi F MAX systems to a LG VRF model). system central protocol for integration with LG central controllers. The PI485 is installed in the Multi F / Multi F MAX outdoor unit.
1. Start up the system and perform a test run. Operate the system in cooling mode for 15 to 20 minutes. 2. Evaluate performance as the system runs, verifying the outdoor unit and all indoor units and BD units (Multi F MAX systems only) are working properly.
LGMV software (PRCTSL1 and PRCTFE1) allows the service technician or commissioning agent to connect a computer USB port to the Multi F / Multi F MAX system’s main printed circuit board (PCB) using an accessory cable without the need for a separate interface device.
Page 172
LG SIMS The SIMs WLAN module and the smart phone app together provide monitoring and trouble- shooting capability for LG Multi F / Multi F MAX systems. SIMs functions only with LG Duct Free products. SIMs can display and graph operational data for the air conditioner system including the indoor unit and the outdoor unit.
Indoor units and branch distribution unit(s) (Multi F MAX only) are installed, properly supported, and located indoors in a non-cor- rosive environment. Multi F / Multi F MAX gravity condensate drain line was connected and routed where it properly drains away or, if installed in a mechanical room, was connected and properly routed to a drain terminal.
Page 179
Power wiring to the Multi F / Multi F MAX outdoor unit was installed per all local electrical code requirements. Power wiring to the indoor units and branch distribution unit(s) (Multi F MAX only) was installed per all local electrical code requirements.
Page 184
20001747 ISO 9001: 2008 LG ELECTRONICS INC. Refer to Service Manuals posted on www.lghvac.com for a full description of all error codes and work-arounds. LG Electronics Products Support 1-888-865-3026 USA LG Electronics, U.S.A., Inc. Follow the prompts for HVAC products.
Page 185
MULTI MULTI CEILING CASSETTE INDOOR UNIT INSTALLATION MANUAL • LMCN077HV 7 kBtu • LCN097HV4 9 kBtu • LCN127HV4 12 kBtu • LMCN185HV 18 kBtu...
551 psi design pressure of R410A. Inadequate piping may fail when pressurized. Allowable Indoor Unit to Outdoor Unit Connections In Multi F / Multi F MAX multi-zone systems, the Ceiling Cassette IDUs can be connected to the Multi F outdoor units (ODUs) listed in the table below.
Page 198
(flare connection) Thermistor for Evaporator Turbo fan Outlet Temperature Liquid pipe connection port (flare connection) Table 6: Multi F Multi Zone Art Cool Mirror Wall-Mounted Indoor Unit Refrigerant Pipe Connection Port Diameters. Model No. Vapor (inch) Liquid (inch) LMCN077HV LCN097HV4 Ø3/8...
IDUs that can be connected to a Multi F system. A typical Multi F Max system consists of an ODU, refrigerant piping, one or two branch distribution units (BDU), and two (2) to eight (8) IDUs.
Field Supplied Refrigerant Piping Type ACR copper is the only approved refrigerant pipe material for use with LG Multi F air conditioning products. ACR rated tubing is the only type that ships with yellow caps. Approved tubing for use with Multi F products will be marked “R410 RATED” along the length of the tube.
Page 207
No Pipe Size Substitutions Use only the pipe size selected by the LATS Multi F pipe system design software or as conveyed in the product installation instructions. Using a different size is prohibited and may result in a system malfunction or failure to work at all.
Multi F MAX Y-Branch Kit PMBL5620 The LG supplied Y-Branch Kit PMBL5620 MUST be used when two branch distribution units are connected to one Multi F MAX system. Field-supplied fittings are not permitted. Each Y-branch kit comes with two (2) Y-branches (one for the liquid line and one for the vapor line) and insulation covers.
Page 209
Tube wall thickness should meet local code requirements and be approved for an operating pressure of 551 psi. If local code does not specify wall thickness, LG suggests using tube thickness per table below. When bending tubing, try to keep the number of bends to a minimum, and use the largest radii possible to reduce the equivalent length of installed pipe;...
Page 219
18,000 Btu/h Ø3/8 → Ø1/2 Connection Socket Figure 46: Possible Outdoor Unit or Branch Distribution Unit (Multi F MAX only) to Indoor Unit Connections. 1. 3/8 in. to 3/8 in. Connection 2. 3/8 in. to 1/2 in. Flare side to indoor unit...
Page 222
Multi F / Multi F MAX System Power Wiring and Communications Cable For both Multi F and Multi F MAX systems, line voltage is wired to the outdoor unit only. The outdoor unit will supply power to the branch distribution units (Multi F MAX systems only) and the indoor units through the power wiring / communications cable.
As always, follow all safety warnings and notes when operating the units using the remote controller. Additionally, all of the Multi F / Multi F Max outdoor models can use the following con- trollers when accompanied with the PI 485 VNet Accessory: •...
Page 225
• Connect the electrical cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. Be sure that the color of the wires at the outdoor unit / BD unit (Multi F MAX systems only) along with the terminal numbers are the same as those for the indoor unit.
Page 233
2. Store a minimal amount of cable in the handy box. Any additional cable should be coiled and stored near the indoor unit control panel. 3. If additional cable length is needed, order a thirty-three (33) foot LG Wired Remote Group Control Extension cable (Model No. PZCWRC1).
Page 234
Hanging the Wired Controller, continued. • Connect indoor unit and wired controller using included connection cable. • Use an LG-manufactured extension cable (sold separately) if the distance between wired remote controller and the indoor unit is >32.8 feet. Figure 72: Indoor Unit to Wired Controller Connection (Controller Appearance May Vary Depending on Model Chosen).
Indoor units and branch distribution unit(s) (Multi F MAX only) are installed, properly supported, and located indoors in a non- corrosive environment. Multi F / Multi F MAX gravity condensate drain line was connected and routed where it properly drains away or, if installed in a mechanical room, was connected and properly routed to a drain terminal.
Page 239
Power wiring to the Multi F / Multi F MAX outdoor unit was installed per all local electrical code requirements. Power wiring to the indoor units and branch distribution unit(s) (Multi F MAX only) was installed per all local electrical code requirements.
Page 244
Who to call for assistance Freight Damage and Unit Replacements Your LG Manufacturer Representative Missing Parts Your LG Manufacturer Representative Freight Damage and Unit Replacements Your LG Manufacturer Representative Received Wrong Indoor Unit Model Your LG Manufacturer Representative Installation, Startup, and Commissioning Technical Assistance 1-888-865-3026 For warranty information, visit www.lghvac.com.
Page 245
20001747 ISO 9001: 2008 LG ELECTRONICS INC. LG Electronics, U.S.A., Inc. LG Customer Information Center, Commercial Products Commercial Air Conditioning Division 1-888-865-3026 USA 4300 North Point Parkway Follow the prompts for commercial A/C products and parts. Alpharetta, Georgia 30022 IM_Multi_F_CeilingCassette_7_16 www.lg-vrf.com...
Page 246
MULTI MULTI CEILING CASSETTE INDOOR UNIT INSTALLATION MANUAL • LMCN077HV 7 kBtu • LCN097HV4 9 kBtu • LCN127HV4 12 kBtu • LMCN185HV 18 kBtu...
551 psi design pressure of R410A. Inadequate piping may fail when pressurized. Allowable Indoor Unit to Outdoor Unit Connections In Multi F / Multi F MAX multi-zone systems, the Ceiling Cassette IDUs can be connected to the Multi F outdoor units (ODUs) listed in the table below.
Page 259
(flare connection) Thermistor for Evaporator Turbo fan Outlet Temperature Liquid pipe connection port (flare connection) Table 6: Multi F Multi Zone Art Cool Mirror Wall-Mounted Indoor Unit Refrigerant Pipe Connection Port Diameters. Model No. Vapor (inch) Liquid (inch) LMCN077HV LCN097HV4 Ø3/8...
IDUs that can be connected to a Multi F system. A typical Multi F Max system consists of an ODU, refrigerant piping, one or two branch distribution units (BDU), and two (2) to eight (8) IDUs.
Field Supplied Refrigerant Piping Type ACR copper is the only approved refrigerant pipe material for use with LG Multi F air conditioning products. ACR rated tubing is the only type that ships with yellow caps. Approved tubing for use with Multi F products will be marked “R410 RATED” along the length of the tube.
Page 268
No Pipe Size Substitutions Use only the pipe size selected by the LATS Multi F pipe system design software or as conveyed in the product installation instructions. Using a different size is prohibited and may result in a system malfunction or failure to work at all.
Multi F MAX Y-Branch Kit PMBL5620 The LG supplied Y-Branch Kit PMBL5620 MUST be used when two branch distribution units are connected to one Multi F MAX system. Field-supplied fittings are not permitted. Each Y-branch kit comes with two (2) Y-branches (one for the liquid line and one for the vapor line) and insulation covers.
Page 270
Tube wall thickness should meet local code requirements and be approved for an operating pressure of 551 psi. If local code does not specify wall thickness, LG suggests using tube thickness per table below. When bending tubing, try to keep the number of bends to a minimum, and use the largest radii possible to reduce the equivalent length of installed pipe;...
Page 280
18,000 Btu/h Ø3/8 → Ø1/2 Connection Socket Figure 46: Possible Outdoor Unit or Branch Distribution Unit (Multi F MAX only) to Indoor Unit Connections. 1. 3/8 in. to 3/8 in. Connection 2. 3/8 in. to 1/2 in. Flare side to indoor unit...
Multi F / Multi F MAX System Power Wiring and Communications Cable For both Multi F and Multi F MAX systems, line voltage is wired to the outdoor unit only. The outdoor unit will supply power to the branch distribution units (Multi F MAX systems only) and the indoor units through the power wiring / communications cable.
As always, follow all safety warnings and notes when operating the units using the remote controller. Additionally, all of the Multi F / Multi F Max outdoor models can use the following con- trollers when accompanied with the PI 485 VNet Accessory: •...
Page 286
• Connect the electrical cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. Be sure that the color of the wires at the outdoor unit / BD unit (Multi F MAX systems only) along with the terminal numbers are the same as those for the indoor unit.
Page 294
2. Store a minimal amount of cable in the handy box. Any additional cable should be coiled and stored near the indoor unit control panel. 3. If additional cable length is needed, order a thirty-three (33) foot LG Wired Remote Group Control Extension cable (Model No. PZCWRC1).
Page 295
Hanging the Wired Controller, continued. • Connect indoor unit and wired controller using included connection cable. • Use an LG-manufactured extension cable (sold separately) if the distance between wired remote controller and the indoor unit is >32.8 feet. Figure 72: Indoor Unit to Wired Controller Connection (Controller Appearance May Vary Depending on Model Chosen).
Indoor units and branch distribution unit(s) (Multi F MAX only) are installed, properly supported, and located indoors in a non- corrosive environment. Multi F / Multi F MAX gravity condensate drain line was connected and routed where it properly drains away or, if installed in a mechanical room, was connected and properly routed to a drain terminal.
Page 300
Power wiring to the Multi F / Multi F MAX outdoor unit was installed per all local electrical code requirements. Power wiring to the indoor units and branch distribution unit(s) (Multi F MAX only) was installed per all local electrical code requirements.
Page 305
Who to call for assistance Freight Damage and Unit Replacements Your LG Manufacturer Representative Missing Parts Your LG Manufacturer Representative Freight Damage and Unit Replacements Your LG Manufacturer Representative Received Wrong Indoor Unit Model Your LG Manufacturer Representative Installation, Startup, and Commissioning Technical Assistance 1-888-865-3026 For warranty information, visit www.lghvac.com.
Page 306
20001747 ISO 9001: 2008 LG ELECTRONICS INC. LG Electronics, U.S.A., Inc. LG Customer Information Center, Commercial Products Commercial Air Conditioning Division 1-888-865-3026 USA 4300 North Point Parkway Follow the prompts for commercial A/C products and parts. Alpharetta, Georgia 30022 IM_Multi_F_CeilingCassette_7_16 www.lg-vrf.com...
Page 307
• Please read this installation manual completely before installing the product. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only. • Please retain this installation manual for future reference after reading it thoroughly. TYPE : Multi Type http://www.lghvac.com www.lg.com P/NO : MFL68280101...
Page 308
FLEX MULTI SPLIT INSTALLATION INSTRUCTIONS...
Page 309
Multi Air Conditioner Installation Manual TABLE OF CONTENTS Required Tools Installation Requirements Installation Parts Provided ...........4 Safety Precautions ..............5 Installation of Indoor, Outdoor Unit ........8 Select the best location ............8 o Level gauge Seaside Applications and Installation ......10 o Screw driver Seasonal Wind And Cautions In Winter......11 o Electric drill Piping length and elevation ..........12...
Installation Parts Provided Installation Parts Provided [Wall mounted / ART COOL Mirror] Type 1 Type 2 Type 3 Type 4 Installation plate Installation plate Installation plate Installation plate Type "B" screw Type "B" screw Type "B" screw Type "C" screw Type "B"...
Product Introduction Safety Precautions To prevent the injury of the user or other people and property damage, the following instructions must be followed. n Be sure to read before installing the air conditioner. n Be sure to observe the cautions specified here as they include important items related to safety. n Incorrect operation due to ignoring instruction will cause harm or damage.
Page 312
Safety Precautions Do not install the product at a place that there Use caution when unpacking and installing. is concern of falling down. • Otherwise, it may result in personal injury. • Sharp edges may cause injury. Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and Do not use Flammable gases.
Page 313
Safety Precautions CAUTION n Installation Install the drain hose to ensure that drain Install the product so that the noise or hot can be securely done. wind from the outdoor unit may not cause any damage to the neighbors. • Otherwise, it may cause water leakage. •...
Safety Precautions Installation of Indoor, Outdoor Unit Read completely, then follow step by step. Select the best location Indoor unit 1. Do not have any heat or steam near the unit. [Wall mounted / ART COOL Mirror] 2. Select a place where there are no obstacles in More than front of the unit.
Page 315
Installation of Indoor, Outdoor Unit Outdoor unit 1. If an awning is built over the unit to prevent di- rect sunlight or rain exposure, make sure that more than heat radiation from the condenser is not re- 600 (23 21/32) stricted.
Installation of Indoor, Outdoor Unit Seaside Applications and Installation 1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced. 2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product.
Installation of Indoor, Outdoor Unit Seasonal Wind And Cautions In Winter - Sufficient measures are required in a snow area or severe cold area in winter so that product can be operated well. - Get ready for seasonal wind or snow in winter even in other areas. - Install a suction and discharge duct not to let in snow or rain.
Page 318
Installation of Indoor, Outdoor Unit 12 Multi Air Conditioner...
Page 319
Installation of Indoor, Outdoor Unit Distributor Piping Type Unit : m(ft) Min length of Max Elevation Max Eleva- Max total length Max length Max length Max Combi- Outdoor Unit Max length each pipe Between each tion of all pipes nation Capacity of each (Main /...
Installation Installation [Wall mounted / ART COOL Mirror] Connecting the piping # Standard / Artcool Mirror Type 1. Prepare the indoor unit's piping and drain hose for installation through the wall. 2. Remove the plastic tubing retainer(see the il- lustration on the right) and pull the tubing and drain hose away from chassis.
Page 321
Installation # Standard Libero / Artcool Libero Type 1. Pull the screw cap at the bottom of the indoor unit 2. Remove the chassis cover from the unit by loosing screws Chassis cover Indoor unit back side view 3. Pull back the tubing holder. Pipe Port 4.
Page 322
Installation Connecting the piping to the indoor unit and drain hose to drain pipe. 1. Align the center of the pipes and suffi- Indoor unit tubing Flare nut Pipes ciently tighten the flare nut by hand. 2. Tighten the flare nut with a wrench. Open-end wrench (fixed) Outside diameter Torque...
Page 323
Installation Wrap the insulation material around the con- Plastic bands Insulation material necting portion. 1. Overlap the connection pipe insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap. Indoor unit pipe Connection pipe 2.
Installation Installation of filters 1) Detach two attached tapes from the plasma filter. Plasma Filter How To Fix The wall you select should be strong and solid enough to prevent vibration 1. Mount the installation plate on the wall with type "A"...
Installation Wiring Connection 1. Connect the wires to the terminals on the con- trol board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Installation [Ceiling Cassette Type] Ceiling dimension and hanging bolt location • The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions. Ceiling Ceiling board Level gauge • Select and mark the position for fixing bolts and piping 585~660(23 1/16~26) (Ceiling Opening) hole.
Installation How to Fix Ceiling Keep the length of the bolt Hanging bolt from the bracket to 40mm(1-9/16 inch) (W3/8 or M10) Flat washer for M10 Air Conditioner body (W3/8 or M10) (accessory) Ceiling board Ceiling board Spring washer (M10) Keep the length of 31~34mm(1.22~1.34inch) between the air conditioner bottom surfac e and the ceiling surface...
Installation Installation of Wired Remote Controller(Optional) 1. Please fix tightly using provided screw after placing remote controller setup board on the place where you like to setup. - Please set it up not to bend because poor setup could take place if setup board bends. Please set up remote controller board fit to the reclamation box if there is a reclamation box.
Page 329
Installation 3. Please fix remote controller upper part into <Connecting order> the setup board attached to the surface of the wall, as the picture below, and then, connect with setup board by pressing lower part. Wall Wall - Please connect not to make a gap at the remote controller Side Side and setup boardʼs upper and lower, right and left part.
Installation Installation of Decorative Panel The decorative panel has its installation direction. Before installing the decorative panel, always remove the paper template. 1. Remove the packing and take out air inlet grille from front panel. Front grille 2. Remove the Corner covers of the panel. Coner cover 3.
Page 331
Installation 5. Fit the corner covers. 6. Open two screws of control panel cover. Screw 7. Connect one display connector and two vane control connectors of front panel to indoor unit PCB. The position marking on PCB is as: Display connector : CN-DISPLAY Vane control connector: CN-VANE 1,2 CN-VANE 1,2 CN-DISPLAY 8.
Installation CAUTION: Install certainly the decorative panel. Cool air leakage causes sweating. ⇨ Water drops fall. Good example Bad example Air conditioner unit Air conditioner Cool air leakage unit (no good) Ceiling Ceiling board board Decorative Decorative panel panel Fit the insulator (this part) and be careful for cool air leakage HEAT INSULATION 1.
Page 333
Installation [Ceiling Concealed Duct/Ceiling Cassette Type] • Drain piping must have down-slope (1/50 to 1/100): be Upward sure not to provide up-and-down slope to prevent rever- Pipe clamp routing sal flow. not allowed • During drain piping connection, be careful not to exert Indoor unit extra force on the drain port on the indoor unit.
Page 334
Installation Attention 1. Possible drain-head height is up to 700mm(27 9/16 inch). So, it must be in- stalled below 700mm(27 9/16 inch). 1/50~1/100 MAX 700mm 2. Keep the drain hose downward up to (27 9/16 inch) 1/50~1/100 inclination. Prevent any upward flow or reverse flow in any part.
Flaring Work and Connection of Piping Flaring Work and Connection of Piping Flaring work Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the fol- Copper Slanted Uneven Rough lowing procedure. tube 1) Cut the pipes and the cable. n Use the accessory piping kit or the pipes purchased locally.
Flaring Work and Connection of Piping Connection of piping - Outdoor Align the center of the piping and sufficiently tighten the flare nut by hand. Connecting pipe order 1) ROOM A~C gas side pipe 2) ROOM A~C liquid side pipe Ø12.7(1/2 inch) Connector Finally, tighten the flare nut with torque wrench...
Page 337
Flaring Work and Connection of Piping • For the units with capacity more than 48 kBtu/h, the installation piping is connectable in four Continuous directions.(refer to figure 1) • When connecting in a downward direction, knock out the knockout hole of the base pan. Torque wrench (refer to figure 2)
Page 338
Flaring Work and Connection of Piping Branch [unit:mm] Model Gas Pipe Liquid Pipe Ø19.05 Ø9.52 Ø19.05 Ø9.52 PMBL5620 Ø9.52 Ø19.05 Y branch To Outdoor Unit To BD Unit • Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.) Horizontal Facing upwards...
Flaring Work and Connection of Piping Installation • This unit may be installed suspended from the ceiling or mounted on the wall. • This unit may only be installed horizontally , as shown in the diagram below.(Side B is facing up) However, it may be freely installed in any direction forward or back, and to the sides.
Flaring Work and Connection of Piping Installation of The Main Unit NOTICE • This unit has two different installation types: (1) Ceiling-suspended type and (2) wall-mounted type. • Choose the proper installation pattern according to the location of installation. • The installation location for printed wiring board can be changed.
Connecting the Cable between Indoor Unit, Distributor Unit and Outdoor Unit Connecting the Cable between Indoor Unit, Distributor Unit and Outdoor Unit Connect the cable to the Indoor unit. Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection.
Connecting the Cable between Indoor Unit, Distributor Unit and Outdoor Unit Connect the cable to the Distributor unit. • Connect refrigerant pipes and connection wires to the appropriate ports maked with matching alphabets (A, B and C) on this unit. •...
Connecting the Cable between Indoor Unit, Distributor Unit and Outdoor Unit Connect the cable to the Outdoor unit. 1. Remove the control cover from the unit by loos- ening the screw. Connect the wires to the terminals on the control Power Power Power...
Page 344
Connecting the Cable between Indoor Unit, Distributor Unit and Outdoor Unit NOTICE 1. Use connection cable NRTL(UL, ETL, CAS…) listed and stranded copper(4) THHN conductors, sunlight (UV) resistant ROHS compliant PVC jacket 600V direct burial listed, approved for wet conditions. Temperature rated for –20℃(-4℉) to 90℃(194℉). And this cable should be enclosed in conduit.
Connecting the Cable between Indoor Unit, Distributor Unit and Outdoor Unit Connection method of the connecting cable(Example) (1) Remove the side panel and knockouts of conduit panel. (for low voltage line) (2) Pull out connection cable through conduit. Conduit (filed supply) (3) After conduit to the panel, fix nut to the opposite Lock nut (field supply)
Checking the Drainage, Insulating the Pipe and Special Piping Applications Checking the Drainage, Insulating the Pipe and Special Piping Applications Checking the drainage 1. Remove the Air Filter. 2. Check the drainage. • Spray one or two glasses of water upon the evaporator.
Air Purging and Evacuation Air Purging and Evacuation Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. 1. Pressure in the system rises. 2. Operating current rises. 3. Cooling(or heating) efficiency drops. 4. Moisture in the refrigerant circuit may freeze and block capillary tubing. 5.
Air Purging and Evacuation Evacuation 1. Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Indoor unit Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. Manifold valve The operation time for evacuation varies with Pressure...
Charging Charging n If installed total piping length is more than standard total length, additional refrigerant charging is necessary. Below standard total piping length, additional refrigerant charging is not required. Multiple Piping Models Unit:m(ft) Standard Total Piping Max total length of all Additional Refrigerant Outdoor Unit Ca- Max length of each...
Page 350
Charging Distributor type Models Additional charge (oz) = (( Total Main piping Length - Main Standard Length ) x 0.55 + (A Room Branch Length – Standard Length ) x 0.22 + (B Room Branch Length – Standard Length ) x 0.22 + (C Room Branch Length –...
Installation PI485 Installation PI485 Fix the PI485 PCB as shown in Fig. Detailed installation method refer to PI485 Installation Manual. 18k Btu/h, 24k Btu/h 36kBtu/h This label is should be applied in the location This label is should be applied in the location where where LGAP(Sub PCB for Central Controller is...
Test Running Test Running - Check that all tubing and wiring have been properly connected. - Check that the gas and liquid side service valves are fully open. Prepare remote control Remove the battery cover by pulling it according to the arrow direction.Insert new batteries making sure that the (+) and (–) of battery are installed correctly.
Function Function Dip S/W Setting If you set the Dip Switch when power is on, the change in setting is not applicable. The changing set- ting is enabled only when Power is reset. Dip Switch Function 1 2 3 4 Normal Operation (No Function) Forced Cooling Operation Wiring Error Check...
Function 18/24(1Ø) kBtu/h 36(1Ø) kBtu/h SW01N DIP-SW 54(1Ø) kBtu/h Forced Cooling Operation Adding the refrigerant in winter. Setting Procedure 1. Set the Dip Switch as follow after shutting the power source down. 2. Reset the power. 3. Check that the Red LED of PCB is on during work. (The indoor unit is operated by force.) 4 Add the specific amount of refrigerant.
Function Wiring Error Check You can check whether or not the wiring is correct. Setting Procedure 1. Set the Dip Switch as follow after shutting the power source down. 2. Reset the power. 3. Check that the Re and Green LED of PCB are on during work. (The indoor unit is oper- ated by force.) 4.
Function Saving Power Consumption Current level. Phase 1Ø Model 18/24k Step1(A) Step2(A) Saving Power Consumption with Mode Lock. Saving Power Saving Power Consumption (step 1) Consumption (step 1) + Mode Lock (Cooling) + Mode Lock (Heating) Saving Power Saving Power Consumption (step 2) Consumption (step 2) + Mode Lock (Cooling)
Function Mode Lock Setting Procedure 1. Set the Dip Switch as follow after shutting the power source down. Only Cooling Mode Only Heating Mode 2. Reset the power. Mode Lock with Night Quiet Mode Mode Lock (Cooling) Mode Lock (Cooling) + Night Quiet Mode + Night Quiet Mode (step 1)
Function PCB Display(18/24k Model Only) It is useful to check the cycle data without LGMV. Operating Method Whenever you push the Tact Switch, the cycle information will be shown as below. h After 1page is displayed, subsequently 2page is displayed. Tact S/W Display Item...
Combination indoor units Combination indoor units The indoor units connectable to the outdoor unit are shown below Model names Outdoor Unit Capacity (Btu/h class) Category Chassis Capacity, kW(kBtu/h Class) 2.1(7) 2.6 (9) 3.5 (12) 4.2(15) 5.3 (18) 7.03 (24) 10.6 (36) Connectable Combination Wall mounted AMNW07GDBL1...
Page 361
1. Please call the installing contractor of your product, as warranty service will be provided by them. 2. If you have service issues that have not been addressed by the contractor, please call 1-888-865-3026. CANADA Service call Number # : (888) LG Canada, (888) 542-2623...