TB6575/TB8575 SuitePRO™
Digital Fan Coil Thermostats

PRODUCT DESCRIPTION

The SuitePRO™ is a family of Digital Fan Coil
thermostats for residential and commercial applications
such as hotels, condominiums, school classrooms, etc.
Four models are available for your application:
• TB6575A1000: 2-pipe or 4-pipe with seasonal/manual/
automatic heat/cool changeover; 120/240 Vac.
• TB6575B1000: 2-pipe only with seasonal or manual
heat/cool changeover; 120/240 Vac.
• TB6575C1000: 2-pipe or 4-pipe with seasonal/manual/
automatic heat/cool changeover; 120/240/277 Vac.
• TB8575A1000: 2-pipe or 4-pipe with seasonal heat/
cool changeover; 24Vac.
All four models are suitable for multiple applications.
Changes in output wiring and external links between
wiring terminals allow you to configure the thermostat for
the appropriate application.
The applications that are available are:
• Heating or Cooling only
• Two pipes: Heat or Cool with Manual Changeover
• Two pipes: Heat or Cool with Seasonal Changeover
(requires optional pipe sensor)
• Two pipes: Heat or Cool with Auxiliary Heat and
Manual or Seasonal Changeover (requires optional
pipe sensor)
• Four pipes: Mixed Manual and Auto Changeover
• Four pipes: Manual Changeover
• Four pipes: Auto Changeover
The fan is controlled from the thermostat. The Low,
Medium, High, or Auto fan settings are easily made with
a press of a key.
Valves and auxiliary electric heaters can be controlled using
a relay or contactor controlled by the system switch.
Installation INSTRUCTIONS

FEATURES

• Simple, intuitive user interface.
• Pre-installed lead wires for fast installation
(TB6575A, TB6575B and TB6575C models only)
• Backlight display permits easy viewing in any
light.
• Four buttons allow manual control of system
Operation, fan speed, and temperature setpoint
adjustment.
• Digital display of ambient temperature, setpoint,
heating or cooling mode, fan status, and remote
setback
• Proportional plus Integral (P+I) control algorithm
for precision temperature regulation.
• Single Setpoint and Heat/Cool setpoint methods
for 4-pipe auto changeover.
• Adjustable maximum heating and minimum
cooling setpoint limits using range stops.
• EEPROM permanently retains user settings,
including setpoints, during power loss (no
batteries required).
• Selectable °C or °F display via Setup button on
thermostat.
• Displayable pipe sensor temperature readout to
aid in troubleshooting.
• Selectable to allow the fan motor to always begin
on high speed to ensure sufficient torque at
startup.
• Option to wire a remote indoor temperature
sensor.
• Freeze protect algorithm turns on heat when
needed.
• Economy Setback options via dry contact or
Activity Sensing
• Advanced fan control with VersaSpeed(TM) fan
ramp algorithm and Auto Fan Reset
62-0278-07

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell SUITEPRO TB6575

  • Page 1: Installation Instructions

    TB6575/TB8575 SuitePRO™ Digital Fan Coil Thermostats INSTALLATION INSTRUCTIONS FEATURES • Simple, intuitive user interface. • Pre-installed lead wires for fast installation (TB6575A, TB6575B and TB6575C models only) • Backlight display permits easy viewing in any light. • Four buttons allow manual control of system operation, fan speed, and temperature setpoint adjustment.
  • Page 2: Specifications

    TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS SPECIFICATIONS Cooling: 22°C to 32°C (72°F to 90°F). Enclosure: Plastic (cover, sub-base, and optional adap- Supply Voltages: tor plate) TB6575A1000 and TB6575B1000: • 120 Vac ±10% at 50/60Hz Junction Box Mounting: Direct mounting on a horizontal •...
  • Page 3: Mounting And Wiring

    TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS The five relays are wired via terminals W, Y, Gh, Gm, and Gl. Relay 1 controls Heat open (W) or Cool open (Y). Relay 2 controls Cool open or Electrical heater output (Y/A). Relays 3, 4, and 5 control the High, Medium, and Low fan speeds respectively (Gh, Gm, and Gl).
  • Page 4 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS (1) Attach the supply wires directly to the termi- Attach the sub-base to the junction box using the nals on the sub-base. See Table 3 on page 5 screws provided. 4. Thoroughly check the wiring to the sub-base before for terminal identification.
  • Page 5 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS • Ps: Pipe sensor (optional) • Sc: Ground (required if remote sensor, pipe sensor, and/or remote setback are connected) • R: 24 Vac power • W/Y: W = Heating; Y = Cooling (2 pipe only) •...
  • Page 6 The TR21 is an optional remote temperature sensor that can be used as an alternative to the internal sensor. In TR21 TR21 addition to the TR21, other Honeywell sensors that use a 20k Ohm curve may be used as the remote sensor. WARNING Risk of electrical shock.
  • Page 7 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS Thermostat Wiring Diagrams L (HOT) The figures in this section illustrate typical wiring for: VALVE • TB6575A1000, TB6575B1000 and TB6575C1000 fan coil thermostats, which are 120/240/277 Vac powered. Refer to Fig. 7–Fig. 13, beginning on page 7, •...
  • Page 8 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS 24 Vac Wiring Diagrams (TB8575) For the TB8575A1000 model, a 24 Vac Class 2 NEMA L (HOT) rated transformer must be used. HEAT VALVE COOL VALVE HEAT VALVE REMOTE SENSOR (HOT) 24 VAC REMOTE SETBACK REMOTE SENSOR REMOTE SETBACK REMOVE PRE-WIRED WIRE FROM TERMINAL 5 (MID FAN SPEED).
  • Page 9 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS VALVE HEAT VALVE COOL VALVE (HOT) 24 VAC (HOT) 24 VAC REMOTE SENSOR REMOTE SENSOR REMOTE SETBACK REMOTE SETBACK PIPE SENSOR POWER SUPPLY. PROVIDE DISCONNECT MEANS AND REMOVE PRE-WIRED WIRE FROM TERMINAL 5 (MID FAN SPEED). OVERLOAD PROTECTION AS REQUIRED.
  • Page 10 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS UP AND DOWN ARROW BUTTONS ºF Set to RoomTemp ºF Heat On Fan On Heat Auto System M27586 M27592 SYSTEM BUTTON BUTTON Fig. 21. Removing the thermostat. Fig. 23. LCD display showing default screen. SETUP Power-up At power-up, the thermostat’s LCD shows all display...
  • Page 11 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS Setup M27585 Fig. 24. Installer Setup (IS) mode screen. Table 4. Installer Setup (IS) Codes and Options. Option Option Description (Default value shown in Code Code Description Value Bold) Notes 120 Vac power supply (Default) Line Voltage Selection 240 Vac power supply...
  • Page 12 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS Table 4. Installer Setup (IS) Codes and Options. (Continued) Option Option Description (Default value shown in Code Code Description Value Bold) Notes Range is 50°F to 72°F. Default is 60°F. Pipe Sensor 50 to Changes to Cool when pipe Threshold for temperature is below...
  • Page 13 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS Table 4. Installer Setup (IS) Codes and Options. (Continued) Option Option Description (Default value shown in Code Code Description Value Bold) Notes 50 to Range is 50°F to 90°F. Default is 50°F. Setpoint Range Stop for Cooling All keys are available (Default) Keypad Lockout...
  • Page 14 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS Table 5 provides the Test codes (IT codes) and values. To Table 5. Installer Test (IT) Codes and Options. enter the IT codes: 1. Press the System (Heat/Cool) button to cycle Code Option through the IT codes, which display in the upper Code Description Value...
  • Page 15: Fan Modes

    TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS BUTTON PRESS SETBACK (IS CODE #19-5) The default remote setback option is for economy setback via a button press on the thermostat. In this mode, the REMOTE SETBACK COOL SETPOINT thermostat can quickly be setback by pressing and UNOCCUPIED DEADBAND holding down the System Mode button for more than 3 COOL SWITCHING POINT...
  • Page 16 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS 2 Pipes with Auto Changeover Table 7. Logic for 2 Pipes with Auxiliary Heat For this application the system switch only provides "Off" Pipe and "Auto". When in "Auto" mode the water temperature Temperature will indicate if the thermostat should operate in heating or After Purge Heat Mode...
  • Page 17 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS For this application, the setpoint settings and deadband are illustrated in Fig. 30. The deadband is changed via IS code #10. COOLING SETPOINT COOL SWITCHING POINT SWITCHING DIFFERENTIAL DEADBAND HEATING SETPOINT SETPOINT M27565 HEAT SWITCHING POINT Fig.
  • Page 18 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS Table 8. Troubleshooting. (Continued) Symptom Possible Cause Action Both the heating and Incorrect System Type Check that the Installer Setup code #2 (System Type) value cooling equipment are selected. matches the installed heating and/or cooling equipment. running at the same Heating and cooling wires Separate the shorted heating and cooling wires.
  • Page 19: Customer Assistance

    This warranty does not cover removal or reinstallation costs. This warranty CUSTOMER ASSISTANCE shall not apply if it is shown by Honeywell that the defect or malfunction was caused by damage which occurred while the product was in the possession of a consumer.
  • Page 20 TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS Aquastat® is a registered trademark of Honeywell International Inc. SuitePRO™ is a trademark of Honeywell International Inc. VersaSpeed™ is a trademark of Honeywell International Inc. Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North ®...