Configuration Frame and Parameterization Frame for the ET 200L
Counter Module –
Bytes 11 to 17
Byte 11
Lower count limit (high byte)
Byte 12
Lower count limit (low byte)
Byte 13
Upper count limit (high byte)
Byte 14
Upper count limit(low byte)
Byte 15
7 6 5 4 3 2
Digital output: activate at
Digital output: logic
0: Not inverted
1: Inverted
Byte 16
Pulse duration [0 to 30]
Byte 17
Hysteresis [0 to 255]
Figure C-12 1COUNT40kHz Counter Module – Purpose of Bytes 11 to 17 of Data Record 130
C-26
The purpose of bytes 11 to 17 of data record 130 for the 1COUNT40kHz
counter module indicated in Figure C-12.
Lower count limit
Upper count limit
1
0
Bit no.
Mode
00: Continuous
01: Single-pass
10: Periodic
Count mode
0: Upward
1: Upward/downward
Comparison value enabling
0: Disable
1: Enable
000: Dispable
001: Comparison value to overflow
010: Comparison value to underflow
011: Comparison value reached as pulse counting upward
100: Comparison value reached as pulse counting downward
101: Comparison value reached as pulse counting upward or downward
Pulse duration in steps of 100 ms
Activate hysteresis of count pulses at output
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c