Optional Operation

1) Two Thermistor System
(1) Open the rear cover of the wired remote-controller to set the mode.
(2) Select one of three selectable modes as follows.
• Position 1:
The room temperature is controlled by the thermistor of the main body.
• Position 2:
The room themperature is controlled by the thermistor of the wired remote-controller, control the
temperature according to the position of wired remote-controller.
• Position 3:
The room temperature is controlled by lower temperature between the temperature of main body and of
remote-controller sensor.
(3) Move the slide switch to set position.
(4) Close the rear cover and check if it works normally.
CAUTION
• Select the position after counselling with a customer.
• In case of cooling mode, room temperature is controlled by the main body sensor.
• To control the room temperature by a wired remote controller, install controller(room temp. sensor) to sense
the temperature more accurately.
• Maunfactured in the position 1.
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Room Temp. sensor
Slide switch for 2 Thermistor
Position 2
REMO
MAIN
Position 1
2TH
Position 3
- 34 -
TH
R13H
R12H
OP5R16H
OP4
CO1H
R15H
OP3 OP2
OP1
R14H
R19H
SW TH
R11H
REMO
MAIN
OP7
2TH
R18H
R17H
OP6
LO
STAND
R03S
HI
R01S
SW
HIGH