hit counter script

Other Information You May Need; C6220 Fresh Air Support - Dell PowerEdge C6220 II Owner's Manual

Hide thumbs Also See for PowerEdge C6220 II:
Table of Contents

Advertisement

Other Information You May Need

WARNING: See the safety and regulatory information that shipped with your
system. Warranty information may be included within this document or as a
separate document.
Getting Started Guide
The
features, setting up your system, and technical specifications.
NOTE: Always check for updates on dell.com/support/home and read the updates
first because they often supersede information in other documents.

C6220 Fresh Air Support

Expanded Operating Temperature
10% of annual
operating hours
1% of annual
operating hours
52
|
About Your System
provides an overview of rack installation, system
5 °C to 40 °C, 5% to 85% RH with 26 °C max. dew point.
For temperatures between 35 °C and 40 °C, de-rate maximum
allowable dry bulb temperature by 1 °C/175 meters above 950
meters (1 °F per 319 feet).
–5 °C to 45 °C, 5% to 90% RH with 26 °C dew point.
For temperatures between 40 °C and 45 °C, de-rate maximum
allowable dry bulb temperature by 1 °C/125 meters above 950
meters (1 °F per 228 feet).
NOTE: When operating in the expanded temperature range,
ambient temperature warnings may be reported in the System
Event Log.
NOTE: No cold start up below 5 °C.
NOTE: The operating temperature specification is for a
maximum altitude of 3048 meters (10,000 feet).
NOTE: 1U and 2U nodes support the 130W (8 core),
130W (4 core) and 135W processors with the specific
configurations of HDD, PCI-E and Mezzanine card.
Refer to the following statements and matrixes of Fresh
Air Support for details.
The numbers of HDD in the tables below list the total
quantity supported per chassis.
No GPU support.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents