hit counter script

Condensate Composition; Regulations; Compliance With Standards And Regulations; Operating Limits Of The Boiler - Bosch KBR16-3 Installation And Service Instructions Manual

Greenstar fs/combi fs
Table of Contents

Advertisement

24 | Regulations

Input/Output
Voltage
Frequency
Max. power consumption (central heating mode)
Max. power consumption (standby mode)
Sound pressure level
Max. supply temperature
Max. permissible operating pressure (P
Permissible ambient temperature
Nominal water capacity (heating)
Weight (without packaging)
Maximum overall dimensions W x H x D
3.19

Condensate composition

The condensate volume and ingredients may change with regionally and
seasonally varying gas quality and air quality. Typically the following
ingredients and concentrations can be expected:
Substance
Ammonium
Lead
Cadmium
Chrome
Halogenated hydrocarbons
Hydrocarbons
Copper
Nickel
Mercury
Sulfate
Zinc
Tin
Vanadium
pH-value
Table 2 Typical condensate composition
6 720 810 590 (2015/05)
) heating
MS
Value in ppm (mg/l)
1.2
0.01
0.001
0.005
0.002
0.015
0.028
0.1
0.0001
1
0.015
0.01
0.001
4.8
Unit
NG
Vac
120
Hz
60
W
205
W
<6
≤ 45
dB (A)
°F ( °C)
190 (88)
psi (bar)
30 (2.07)
°F ( °C)
32 - 122 (0 - 50)
Gal (L)
0.925 (3.5)
lbs (kg)
136.5(62)
11/
inch
23
x 41
16
(mm)
602 x 1048 x 555
4
Regulations
Observe all rules, regulations, standards and guidelines
applicable to the installation and operation of this
appliance according to local, state and federal
regulations.
In the Commonwealth of Massachusetts, this appliance
must be installed by a licensed plumber and gas fitter.
Valves external to the boiler must be fitted with
T-handles and condensate piping must be installed in
accordance with the State Plumbing Code.
4.1

Compliance with standards and regulations

The installation must conform to the requirements of the authority
having jurisdiction or, in the absence of such requirements, to the latest
edition of the National Fuel Gas Code, ANSI Z223.1./NFPA 54. In
Canada, installation must be in accordance with the requirements of
CAN/CSA B149.1, Natural Gas and Propane Installation Code.
This floor standing condensing gas boiler complies in its design and
mode of operation with the American National Standard ANSI Z21.13/
CSA4.9, latest edition for Gas Fired Low Pressure Steam and Hot Water
Boilers.
Other confirmed approvals and certifications are indicated by labels on
the boiler.
Where required by the authority having jurisdiction, the installation must
conform to the Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1.
Install CO detectors per local regulations. Boiler requires yearly
maintenance ( chapter 15, page 65).
4.2

Operating limits of the boiler

The heat exchanger has been designed and certified in accordance with
the ASME Boiler and Pressure Vessel Code, Section IV.
Maximum boiler temperature
Maximum operating pressure
Table 3 Operating limits
The hot water distribution system must comply with all applicable codes
and regulations. When replacing an existing boiler, it is important to
check the condition of the entire hot water distribution system to ensure
safe operation. Common practice calls for inspecting an existing system
in its entirety and bringing it up to code. All pipe work should be properly
cleaned and flushed.
LPG (Propane)
120
60
205
<6
≤ 45
190 (88)
30 (2.07)
32 - 122 (0 - 50)
0.925 (3.5)
136.5(62)
1/
7/
11/
1/
x 21
23
x 41
x 21
4
8
16
4
602 x 1048 x 555
190 °F (88 °C)
30 psi (2.07 bar)
Greenstar FS
7/
8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kbr28-3Kbr35-3Kwb28-3Kbr42-3Kwb35-3Kwb42-3 ... Show all

Table of Contents

Save PDF